Specifications, Dimensional information, Recovery capacities – Rheem HE80-130LP User Manual

Page 2: Booster models, Maximum delivery, All dimensions shown in english and metric

Advertising
background image

2

SPECIFICATIONS

DIMENSIONAL INFORMATION

All dimensions shown in English and Metric

MODEL

WATER CONNECTIONS

APPROX

NUMBER

UNITS

HEIGHT

WIDTH

DEPTH

VENT

INLET

OUTLET

SHIPPING WT.

inches

42

23 1/2

32

2

1

1

175 lbs.

mm

1067

597

813

51

25

25

79 kgs

inches

42

23 1/2

32

3

1

1

175 lbs.

mm

1067

597

813

76

25

25

79 kgs

inches

72

23 1/2

32

3*

1-1/2

1-1/2

235 lbs.

mm

1854

597

813

76

38

38

106 kgs

inches

73

27

36

3*

1-1/2

1-1/2

405 lbs.

mm

1854

686

914

76

38

38

184 kgs

All models require a 120V power source.
* 130,000 Btu models are certified to be installed with 2” venting.

HE45-100
HE45-130

HE45-160
HE45-199

HE80-130
HE80-160
HE80-199
HE119-130
HE119-160
HE119-199

RECOVERY CAPACITIES

Recovery in U.S. Gallons/Hr. (GPH) and Liters/Hr. (LPH) at Various Temperature Rises

MODEL

INPUT (BTU/HR)

THERMAL

40°F

50°F

60°F

70°F

80°F

90°F

100°F

110°F

120°F

NUMBER

NAT. & LP

EFFICIENCY

UNITS

(22.2°C)

(27.8°C)

(33.3°C)

(38.9°C)

(44.4°C)

(50.0°C)

(55.6°C)

(61.1°C)

(66.7°C)

100,000

95%

GPH

288

230

192

165

144

128

115

105

96

LPH

1090

872

726

623

545

484

436

396

363

130,000

95%

GPH

374

299

249

214

187

166

150

136

125

LPH

1417

1133

944

809

708

630

567

515

472

160,000

95%

GPH

461

368

307

263

230

205

184

167

154

LPH

1744

1395

1162

996

872

775

697

634

581

199,000

95%

GPH

573

458

382

327

286

255

229

208

191

LPH

2169

1735

1446

1239

1084

964

867

789

723

Recovery rating is based on thermal efficiencies obtained in an AGA certified laboratory.

0" CLEARANCE TO
COMBUSTIBLES ON ALL
ADVANTAGE PLUS UNITS,
HOWEVER, A 24"
CONTROL PANEL SER-
VICE CLEARANCE IS
RECOMMENDED.

HE45-100

HE45-130
HE80-130
HE119-130

HE80-160
HE119-160

HE80-199
HE119-199

BOOSTER MODELS

Recovery in U.S. Gallons/Hr. (GPH) and Liters/Hr. (LPH)

MODEL

INPUT (BTU/HR)

THERMAL

40°F

50°F

60°F

70°F

80°F

90°F

100°F

110°F

120°F

130°F

140°F

NUMBER

NAT. & LP

EFFICIENCY

UNITS

(22.2°C)

(27.8°C)

(33.3°C)

(38.9°C)

(44.4°C)

(50.0°C)

(55.6°C)

(61.1°C)

(66.7°C)

(72.2°C)

(77.8°C)

HE45-160

160,000

95%

GPH

461

368

307

263

230

205

184

167

154

142

132

LPH

1744

1395

1162

996

872

775

697

634

581

536

498

HE45-199

199,000

95%

GPH

573

458

382

327

286

255

229

208

191

176

164

LPH

2169

1735

1446

1239

1084

964

867

789

723

667

620

All models exceed the minimum NAECA energy efficiency requirements of ASHRAE 90.1b-1989, 1992 requirements.

MAXIMUM DELIVERY

In U.S. Gallons and Liters (Includes useable storage and recovery for indicated times)

MODEL

GALLONS/

MAX.

INPUT (BTU/HR)

TEMP.

5

10

15

20

30

45

1

2

3

MIN. TO RECOVER

NUMBER

LITERS

SETPOINT

NAT. & LP

RISE

UNITS

MIN.

MIN.

MIN.

MIN.

MIN.

MIN.

HR.

HR.

HR.

CONTENTS

HE45-100

45

160º

100,000

100°F

GAL.

41

51

60

70

89

118

147

262

377

23

170

55.6°C

LTR.

156

192

228

265

337

446

555

991

1427

HE45-130

45

160º

130,000

100°F

GAL.

44

56

69

81

106

144

181

331

481

18

170

55.6°C

LTR.

166

214

261

308

403

544

686

1253

1819

HE80-130

80

160º

130,000

100°F

GAL.

68

81

93

106

131

168

206

355

505

32

303

55.6°C

LTR.

259

306

354

401

495

637

779

1345

1912

HE119-130

119

160º

130,000

100°F

GAL.

96

108

121

133

158

196

233

383

532

48

450

55.6°C

LTR.

363

410

457

504

599

750

882

1449

2015

HE45-160

45

180º*

160,000

100°F

GAL.

47

62

78

93

124

170

216

400

584

15

170

55.6°C

LTR.

177

235

294

352

468

642

817

1514

2211

HE80-160

80

160º

160,000

100°F

GAL.

71

87

102

117

148

194

240

424

609

26

303

55.6°C

LTR.

270

328

386

444

561

735

909

1607

2304

HE119-160

119

160º

160,000

100°F

GAL.

99

114

129

145

175

221

268

452

636

39

450

55.6°C

LTR.

373

432

490

548

664

838

1013

1710

2408

HE45-199

45

180º*

199,000

100°F

GAL.

51

70

89

108

146

203

261

490

719

12

170

55.6°C

LTR.

192

264

336

408

553

770

987

1854

2721

HE80-199

80

160º

199,000

100°F

GAL.

75

94

113

132

171

228

285

514

743

21

303

55.6°C

LTR.

284

357

429

501

646

863

1079

1947

2814

HE119-199

119

160º

199,000

100°F

GAL.

102

121

141

160

198

255

312

542

771

31

450

55.6°C

LTR.

338

460

532

604

749

966

1183

2050

2918

All models have a maximum setpoint of 160°F with the exception of the HE45-160 and HE45-199 booster models. The HE45-160 and HE45-199 have a maximum setpoint of 180°F.

* NOTE: The 180º F models are shipped with all necessary components for an approved installation (see Booster Installation Kit for component list.)

Advertising