Venting Samples

INTAKE

EXHAUST

HOT

COLD

24"

MIN.

10'
-

0"
MIN.

MAINTAIN 12" MIN.
(18" MIN. FOR CANADA)
CLEARANCE ABOVE HIGHEST
ANTICIPATED SNOW LEVEL.
MAXIMUM OF 24" ABOVE ROOF

3" PVC

3" ABS
MIN. 84"
REQ'D

FLOOR MOUNTED
PIPE SUPPORT

FIGURE 6 - VERTICAL ROOF VENTING

3" 4" (FRONT VIEW)

MIN. 10'

REQ'D

3' TO 4" PVC
REDUCING
COUPLING

4" PVC

HOT

COLD

HOT

COLD

FLOOR MOUNTED
PIPE SUPPORT

3" PVC

MIN. 10'

REQ'D

3" ABS
MIN. 84"
REQ'D

3' TO 4" PVC
REDUCING
COUPLING

4" PVC

12"

8" MIN.

INTAKE

EXHAUST

FLOOR MOUNTED
PIPE SUPPORT

3" ABS
MIN. 84"
REQ'D

3" PVC

MIN. 10'

REQ'D

4" PVC

MAX. 125'

EQUIVALENT

FEET OF 4"

3' TO 4" PVC
REDUCING
COUPLING

3' TO 4" PVC REDUCING COUPLING
TO UTILIZE V1000 SIDE WALL VENT TERMINAL

INTAKE

EXHAUST

EXHAUST

OPTIONAL V1000

VENT KIT

(SIDE VIEW)

V1000 SIDE WALL

VENT KIT

(FRONT VIEW)

FRESH AIR

FOR

COMBUSTION

FIGURE 5 - SIDE WALL VENTING

3" 4" (SIDE VIEW)

FIGURE 7 - SIDE WALL VENTING USING THE V1000 VENT KIT

3" 4" 3" (SIDE VIEW)*

*NOTE: THE ONLY TIME 4" CAN BE REDUCED BACK
TO 3" IS WHEN THE V1000 VENT KIT IS UTILIZED.