Rheem HE80-130LP User Manual

Page 28

Advertising
background image

28

LED Flashing

Controlling Function

Possible Cause

Service Remedy

LINE

Check Breaker

Turn breaker ON

Wiring disconnected

Check wiring

Does not have 120 VAC

Reseat plugs on control
module

24 VAC

Transformer wiring problem

Repair wiring

Transformer is defective

Replace transformer

Does not have 24 VAC

Reseat plugs on control
module

ECO/VENT SWITCH

Check connector. Repair wiring

Check connector. Repair wiring

Water in tank too hot

Venting has a problem

Check venting for obstructions

Press reset button and recheck.

PRESSURE SWITCH

Combustion air blockage

Combustion air blockage

Blower not operating

Air switch stuck open or closed

Replace air switch

WATER TEMPERATURE

Temp probe wiring is unplugged

Check connector or repair wiring

Probe open internally

Replace probe

Probe wiring shorted

Repair short

or

Probe shorted internally

Replace probe

no or low water in tank

GAS VALVE

Check wire and connection at
burner

Ignition lock out

Check and reseat connections

No flame rectification

Gas valve shut OFF

Turn gas valve ON

Clogged gas valve

Replace gas valve

Faulty gas valve

Replace gas valve

Defective control

Replace control

Gas valve improperly adjusted

Adjust gas valve correctly

BLOWER

No power to blower

Check for power to blower

Power to blower

Blower is bad

Repair or replace wiring
Replace blower

IGNITOR

No power to ignitor

Check for power to ignitor

Power to ignitor

Ignitor is bad

Repair or replace wiring

Replace ignitor

CONTROL HEALTH

System problem on circuit board

System board OK

Polarity is reversed

Correct polarity

Poor or incomplete ground

Proper ground and polarity

Ensure adequate grounding to unit
and in electrical circuit

GREEN LED ON MAIN
CONTROL BOARD

Monitors polarity and ground circuit.
ON when ground and polarity are
OK.
Attempts to fire for 4-6 seconds; then

Ignitor current draw is too low.
See ignitor lockout on page 17

Press red reset button. If error
occurs repeatedly, replace main
control board

Monitors ignitor element output. ON
when power is applied to the ignitor

Monitors the controllers hardware
(circuit boards) and software. ON
when controller is functioning OK

Broken or corroded burner ground
wire
Connectors on controlled panel
unplugged

Unit will make three (3) successive
trials; then lock out.

Monitors the blower motor output.
ON when power is applied to the
blower.

Monitors water temperature inside
the tank (Thermostat). ON when the
water temp drops below set point
(temperature setting).

Something is wrong with the

temperature probe

Monitors the gas valve output. ON
when power is applied to the gas
valve

or

Monitors the air pressure switch. ON
when the pressure switch is closed.
Means there is sufficient combustion
airflow.

Check intake and exhaust piping
and flue for obstructions
Check and repair blower wiring;
replace blower motor

Normal when water gets too hot.
Cool tank. Determine cause for

over temperature.

Monitors water temperature in the
tank and exhaust vent temperature.

To diagnose, must determine which
function is at fault.

Vent switch overtemp switch is
open
No or not enough water in tank.

Check orifices to insure they match

fuel type.

Water in tank is too hot (ECO is
activated). Check water temp in
tank on display board

Monitors incoming AC line voltage.
ON when line voltage is present.

Plugs on module disconnected or
loose

Monitors incoming voltage from the
transformer. ON when secondary 24
VAC is present.

Monitors the ECO switch. ON when
ECO switch is closed (normal
position).

Water temp probe unplugged or
damaged
Vent temp probe unplugged or
damaged

or

Water in tank too low

Make sure tank is full of water.

Display Board LEDs

What they mean, controller functions, possible causes and suggested service remedies.