Roberts Gorden UltraVac NEMA 4 User Manual

Page 21

Advertising
background image

SECTION 4: T

YPICAL

E

XTERNAL

D

IAGRAMS

15

SECTION 4: TYPICAL EXTERNAL DIAGRAMS
FIGURE 10: Central Controller Communication Equalization Wiring

+

-

1

+

-

2

+

-

4

+

-

3

+

-

5

+

-

6

+

-

7

+

-

8

+

-

+

-

REF

RS485 COMM

REF

+

-

1

+

-

2

+

-

3

+

-

4

METER INPUTS

UNIVERSAL INPUTS

IN

OUT

ADDRESS

RESET

10VDC

499 OHM

OFF
ON

OUT
IN

G

IN

OUT

G

G

G

+5

+32

AUX POWER

RS232 DIRECT

RI

CD

OH

CPU

+-

1

+-

2

+-

3

+-

4

Communications Circuit Equalizer Wiring
(included, must be field installed)

RED

BLACK

RED

BLACK

120 ohm resistor (included w/ P/N 100800450)

Shrinkwrap

All ULTRAVAC™ Central Controllers are shipped with a communication equalization cable
(P/N 10080450). The cable is supplied to equalize and balance the circuitry of the communications on
the controller network that may be experiencing noise or transient voltage levels. Connect the communi-
cation equalization cable as shown below to the first or the last controller on the data bus.

This connector will plug into the right set of
RS-485 +/- terminals on this board as shown.

Description

Part Number

Comms Equalization Cable

10080450