5.5 Communications Between Multiple ROBERTS GORDON

®

ULTRAVAC™ Controllers

If more than one ROBERTS GORDON

®

ULTRA-

VAC™ Controller is installed in a building, the
controllers’ RS-485 communications must be wired in
series. See Page 25, Figure 18. Connect the
RS-485 terminal on controller

#

1 to the RS-485

terminal on controller

#

2 and so on in a daisy chain

fashion. For communication cable requirements,
See Page 12, Section 3.3.5

From a PC, by dialing into the modem on controller

#

1

or by connecting to controller

#

1 via RS-485

converter or TCP/IP communication module, the

system status and settings can be viewed for any of
the controllers on the network.

The control board identification dip switch must be
set on each ROBERTS GORDON

®

ULTRAVAC™

Controller. See Page 25, Figure 18 for dip switch
settings. Contact Roberts-Gordon or your
ROBERTS GORDON

®

independent distributor, if

more than 20 controllers are connected.

FIGURE 18: Communications Between Multiple Controllers

+-

1

+-

2

+-

4

+-

3

+-

5

+-

6

+-

7

+-

8

+-

+-

REF

24V

A

C

L2

NO

NC

C

NO

NC

C

NO

NC

C

NO

NC

C

NO

NC

C

NO

NC

C

NO

NC

C

NO

NC

C

RS485 COMM

REF

+-

1

+-

2

+-

3

+-

4

METER INPUTS

UNIVERSAL

INPUTS

IN

OUT

ADDRESS

RESET

10VDC

499 OHM

OFF

ON

OUT

IN

G

IN

OUT

G

G

G

+5

+32

AUX POWER

RS232 DIRECT

RI

CD

OH

CPU

L1

PWR

+-

1

+-

2

+-

4

+-

3

+-

5

+-

6

+-

7

+-

8

+-

+-

REF

24V

AC

L2

NO

NC

C

NO

NC

C

NO

NC

C

NO

NC

C

NO

NC

C

NO

NC

C

NO

NC

C

NO

NC

C

RS485 COMM

REF

+-

1

+-

2

+-

3

+-

4

METER INPUTS

UNIVERSAL

INPUTS

IN

OUT

ADDRESS

RESET

10VDC

499 OHM

OFF

ON

OUT

IN

G

IN

OUT

G

G

G

+5

+32

AUX POWER

RS232 DIRECT

RI

CD

OH

CPU

L1

PWR

+-

1

+-

2

+-

4

+-

3

+-

5

+-

6

+-

7

+-

8

+-

+-

REF

24V

A

C

L2

NO

NC

C

NO

NC

C

NO

NC

C

NO

NC

C

NO

NC

C

NO

NC

C

NO

NC

C

NO

NC

C

RS485 COMM

REF

+-

1

+-

2

+-

3

+-

4

METER INPUTS

UNIVERSAL

INPUTS

IN

OUT

ADDRESS

RESET

10VDC

499 OHM

OFF

ON

OUT

IN

G

IN

OUT

G

G

G

+5

+32

AUX POWER

RS232 DIRECT

RI

CD

OH

CPU

L1

PWR

RS 485

Wiring

Central Controller

(controller

#

1)

Satellite Controller

(controller

#

2)

To Additional
Controllers

Wiring

to RS 485
Converter

at PC

(optional)

Dedicated

Outside

Phone Line

(optional)

Satellite Controller

(controller

#

3)

Dip Switch

#

1 and

#

2

Set to ON
(controller

address

#

3)

1 2 3 4 5 6 7 8

Dip Switch

#

2

Set to ON
(controller

address

#

2)

1 2 3 4 5 6 7 8

To RJ11

connection on

TCP/IP

Module

(optional)

Dip Switch

#

1

Set to ON
(controller

address

#

1)

Modem

Chip

1 2 3 4 5 6 7 8

Ground
Shield

Join Shields -
Do Not Ground

Join Shields -
Do Not Ground

Controller

Number

Dip Switch Order (1,2,3,4,5,6,7,8)

Values (1=ON, 0=OFF)

11

11010000

12

00110000

13

10110000

14

01110000

15

11110000

16

00001000

17

10001000

18

01001000

19

11001000

20

00101000

Controller

Number

Dip Switch Order (1,2,3,4,5,6,7,8)

Values (1=ON, 0=OFF)

1 (Central Controller)

10000000

2

01000000

3

11000000

4

00100000

5

10100000

6

01100000

7

11100000

8

00010000

9

10010000

10

01010000