16 figure 11: roberts gordon, Ultravac™ central controller external wiring, Outdoor sensor bms enable (optional) – Roberts Gorden UltraVac NEMA 4 User Manual

Page 22: Pressure switch (pump), M16/12.p

Advertising
background image

ROBERTS GORDON

®

ULTRAVAC™ C

ONTROLLER

I

NSTALLATION

M

ANUAL

16

FIGURE 11: ROBERTS GORDON

®

ULTRAVAC™ Central Controller External Wiring

+

- 1

2

4

3

5

6

7

8

+

-

+-REF

24V

AC

L2

RS485 COMM

REF

+-

1

+-

2

+-

3

+-

4

METER INPUTS

UNIVERSAL

INPUTS

IN

OUT

ADDRESS

RESET

10VDC

499 OHM

OFF

ON

OUT

IN

G

IN

OUT

GGG

+5

+32

AUX POWER

RS232 DIRECT

RI

CD

OH

CPU

L1

PWR

Separate line and low voltage circuits.

Do not run line voltage wiring through bottom

section of enclosure that houses the control board.

Do not run low voltage wiring through top section

of enclosure that houses the relay board.

Do not run line and low voltage wiring

in the same conduit.

NOTE 1: This diagram applies to the Central

Controller (controller #1) only. For all Satellite Controllers see Satellite Controller External Wiring Diagram. Central Controller

(controller #1) requires outdoor sensor wiring and either modem, RS-485 converter wiring, or TCP/IP module wiring.

NOTE 2: Twist shield wires for both RS-485 communication cables together and ground at central panel only. On controller #1 only,

connect these twisted shield wires to ground. For VFD 0-10 V signal wiring, connect shield wire to ground at the controller only.

NOTE 3: 120 V 1 Ø 50-60 Hz supply for 120 V VFD model. 230V 1 Ø 50-60 Hz supply for 230 V VFD model. 460 V 3 Ø 50-60 Hz

supply for 460 V VFD model. See VFD rating plate for required input. Repetitive cycling of a disconnect or input contactor
(more than once every two minutes) may cause damage to the drive.

NOTE 4: Zone 3 Sensor(not shown) wiring is as follows: SEN output to analog input 3; SET output to analog input 6;

O/R output to meter input 3; +/- outputs to +32 V/GND inputs.

NOTE 5: Internal pre-wiring not shown.

NOTE 6: Wiring from 32 V terminals on the controller to sensor power terminals "+" and "-" is polarity sensitive.

NOTE 7: All three power output wires from terminals U, V, and W to the pump motor must be kept tightly bundled and run in a
separate conduit away from all other power and control wiring.

Outdoor

Sensor

BMS Enable

(optional)

NC C NO

To Satellite Controller

RS-485

(see NOTE 2)

Zone 1

Sensor

(see NOTE 6)

120 V

1 Ø

60 Hz

POWER

L1

L2

GRD

OUTPUT 1

L1

L2

GRD

OUTPUT 2

L1

L2

GRD

OUTPUT 3

L1

L2

GRD

OUTPUT 4

L1

L2

GRD

OUTPUT 5

L1

L2

GRD

OUTPUT 6

L1

L2

GRD

OUTPUT 7

L1

L2

GRD

OUTPUT 8

L1

L2

GRD

Pressure
Switch (Pump)

Phone Line

for Modem

(optional)

(see NOTE 1)

To RS-485
Converter at PC
(optional)
(see NOTE 1 & 2)

Pressure Switch
(Optional Outside Air Blower)

Zone 2

Sensor

(see NOTE 6)

+

-

O/R

SET

SEN

+ -

O/R

SET

SEN

Electrical wiring connections indicated by a dot;

Ground Shield (one end only) indicated by;

+

-

(See

NOTE 2)

Continued

On Next

Page

+ -

1

+ -

2

+ -

3

+ -

4

NC C NO

NC C NO

NC C NO

NC C NO

NC C NO

NC C NO

NC C NO

NC C NO

+

-

+

-

+

-

+

-

+

-

+

-

+

-

M16/12.P

Advertising