ROBERTS GORDON

®

ULTRAVAC™ C

ONTROLLER

I

NSTALLATION

M

ANUAL

32

Step 7.1.3 After setting end vent vacuums between
2.5" wc and 3.0" wc, while all the burners are still
operating, use the down arrow button on the VFD to
reduce the frequency of the output signal to the
pump. Reduce the frequency of the VFD until the
manometer at each of the end vents reads 1.0" wc -
1.2" wc Make note of this frequency setting below.
The frequency is found on the VFD’s LCD screen.

1.0" w.c. - 1.2" wc VFD Frequency Setting

Step 7.1.4 Return to the PC and click the pump and
zones to "OFF".

Step 7.1.5 Using the procedure described in on Page
27, Section 6.1.1

through Section 6.1.5, alter the fol-

lowing parameters on the VFD:

Step 7.1.6 Return to the PC and click the vacuum
pump and three zones to "AUTO", then click exit.

Parameter

Number

Parameter

Name

Factory

Default

New

Setting

P05

Standard

Speed

Source

01

03

P45

Speed at
Minimum

Signal

0.0Hz

Frequency

Setting noted in

Section 7.1.3

P46

Speed at

Maximum

Signal

60.0Hz

Frequency

Setting noted in

Section 7.1.2

Record Frequency Setting Here: