18 figure 12: roberts gordon, Ultravac™ satellite controller external wiring, Bms enable (optional) – Roberts Gorden UltraVac NEMA 4 User Manual

Page 24: Zone 2 sensor

Advertising
background image

ROBERTS GORDON

®

ULTRAVAC™ C

ONTROLLER

I

NSTALLATION

M

ANUAL

18

FIGURE 12: ROBERTS GORDON

®

ULTRAVAC™ Satellite Controller External Wiring

ADDRESS

RESET

10VDC

499 OHM

OFF

ON

OUT

IN

RI

CD

OH

CPU

BMS Enable

(optional)

NC C NO

To Satellite Controller

RS-485

(See NOTE 2)

120 V

1 Ø

60 Hz

POWER

L1

L2

GRD

OUTPUT 1

L1

L2

GRD

OUTPUT 2

L1

L2

GRD

OUTPUT 3

L1

L2

GRD

OUTPUT 4

L1

L2

GRD

OUTPUT 5

L1

L2

GRD

OUTPUT 6

L1

L2

GRD

OUTPUT 7

L1

L2

GRD

OUTPUT 8

L1

L2

GRD

Pressure
Switch (Pump)

J

oin Shields - Do

N

ot Gr

o

u

nd

From previous
controller RS-485
(See NOTE 2)

Pressure Switch
(Optional Outside Air Blower)

Zone 1

Sensor

(see NOTE 6)

Zone 2

Sensor

(see NOTE 6)

+

-

O/R

SET

SEN

O/R

SET

SEN

+

-

Electrical wiring connections indicated by a dot;

(See NOTE 2)

Continued

On Next

Page

Separate line and low voltage circuits.

Do not run line voltage wiring through bottom

section of enclosure that houses the control board.

Do not run low voltage wiring through top section

of enclosure that houses the relay board.

Do not run line and low voltage wiring

in the same conduit.

NOTE 1: This diagram applies to the Satellite Controller only.

The Satellite Controller does not require modem, RS-485 converter wiring to the PC, TCP/IP module wiring, or outdoor sensor wiring.

For Central Controller see Central Controller External Wiring Diagram.

NOTE 2: Twist shield wires for both RS-485 communication cables together and ground at central panel only. On controller #1 only,

connect these twisted shield wires to ground. For VFD 0-10 V signal wiring, connect shield wire to ground at the controller only.

NOTE 3: 120 V 1 Ø 50-60 Hz supply for 120 V VFD model. 230V 1 Ø 50-60 Hz supply for 230 V VFD model. 460 V 3 Ø 50-60 Hz

supply for 460 V VFD model. See VFD rating plate for required input. Repetitive cycling of a disconnect or input contactor (more
than once every two minutes) may cause damage to the drive.

NOTE 4: Zone 3 Sensor(not shown) wiring is as follows: SEN output to analog input 3; SET output to analog input 6;

O/R output to meter input 3; +/- outputs to +32 V/GND inputs.

NOTE 5: Internal pre-wiring not shown.

NOTE 6: Wiring from 32 V terminals on the controller to sensor power terminals "+" and "-" is polarity sensitive.

NOTE 7: All three power output wires from terminals U, V, and W to the pump motor must be kept tightly bundled and run in a

separate conduit away from all other power and control wiring.

24V

AC

L2

L1

PWR

NC C NO

NC C NO

NC C NO

NC C NO

NC C NO

NC C NO

NC C NO

NC C NO

+-

+

-

REF

RS485 COMM

REF

+-

1

+-

2

+-

3

+-

4

METER INPUTS

IN

OUT

G

IN

OUT

G

G

G

+5

+32

AUX POWER

RS232 DIRECT

+

- 1

2

4

3

5

6

8

UNIVERSAL

INPUTS

+

-

+

-

+

-

+

-

+

-

+

-

+

-

7

Ground Shield (one end only) indicated by;

M16/12.P

Advertising