FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater

17

INSTALLATION

LOUVRE

INSTALLATION

Attach the top & bottom louvres to the side stove

panel using 2 screws per side.

GAS PIPE PRESSURE

TESTING

The appliance must be isolated from the gas

supply piping system by closing its individual

manual shut-off valve during any pressure

testing of the gas supply piping system at test

pressures equal to or less than 1/2 psig. (3.45

kPa). Disconnect piping from valve at pres-

sures over 3.45 kPa.

The manifold pressure is controlled by a regu-

lator built into the gas control, and should be

checked at the pressure test point.

Note: To properly check gas pressure,

both inlet and manifold pressures

should be checked using the valve

pressure ports on the valve.

1) Make sure the valve is in the "OFF" position.

2) Loosen the "IN" and/or "OUT" pressure

tap(s), turning counterclockwise with a 1/

8" wide flat screwdriver.

3) Attach manometer to "IN" and/or "OUT"

pressure tap(s) using a 5/16" (8mm) ID

hose.

4) Light the pilot and turn the valve to "ON"

position. Read manometer.

5) The pressure check should be carried out

with the unit burning and the setting should

be within the limits specified on the safety

label.

6) When finished reading manometer, turn off

the gas valve, disconnect the hose and

tighten the screw (clockwise) with a 1/8"

flat screwdriver. Note: Screw should be

snug, but do not over tighten

S.I.T. Valve Description

1) On-Off Solenoid Valve EV1
2) On-Off Solenoid Valve EV2
3) Inlet Pressure Test Point
4) Outlet Pressure Test Point
5) Connection for Pressure Regulator/Com-

bustion Chamber Compensation

6) Pressure Regulator for Minimum and Max-

imum Outlet Pressure

7) Gas Outlet Pressure Electric Modulator
8) Pilot Outlet
9) Main Gas Outlet
10) Side Outlet