Example 3: Scaling with Current/Voltage Transducer (Process) Input.

The following example include details for a specific scenario in
which a 4 - 20 mA input is to be represented as a measurement
of 0 - 100 percent.

Press

d

41) Press

d at the IN.RD prompt. Display shows IN!1 Input 1

Submenu.

Press

d

42) Display shows Input 1 value with 1

st

digit flashing.

Press

b & c 43) Use b and c buttons to enter IN!1 value.

The

IN!1 value = min. input value x conversion number

from Table 3.1
Enter 4 mA as 4 (mA) x 500 = 2000

Press

d

44) Display advances to

RD!1 Reading 1 Submenu.

Press

b & c 45) Use b and c buttons to enter RD!1 value.

This value corresponds to Input 1 in terms of some meaningful
engineering units. To show 4 mA as zero percent enter

RD!1

value = 0000.

Press

d

46) Display

IN!2 Input 2 Submenu.

Press

d

47) Display shows

IN!2 Input 2 value with 1

st

digit flashing.

The

IN!2 value = max. input value x conversion number

from Table 3.1
Enter 20 mA as 20 (mA) x 500 = 10000 (entered as 9999)

Press

b & c 48) Use b and c buttons to enter IN!2 value.

Press

d

49) Display advances to

RD!2 Reading 2 Submenu.

Press

b & c 50) Use b and c buttons to enter RD!2 value.

To show 20 mA as 100 percent enter

RD!2 value = 0100

Press

d

51) Display flashes

STRD stored message momentarily and

then advances to

ALR1 only, if a change was made, otherwise

advances to

ALR1 Alarm 1 Menu.