Linearization Points
Up to 10 Linearization Points

Configuration
Single-ended

Polarity
Unipolar

Step Response
0.7 sec for 99.9%

Decimal Selection
None, 0.1, 0.01 or 0.001

Setpoint Adjustment
-1999 to 9999 counts

Span Adjustment
0.001 to 9999 counts

Offset Adjustment
-1999 to +9999

CONTROL
Action
Reverse or direct

Modes
Time and Amplitude Proportional
Control Modes; selectable Manual or
Auto PID, Proportional, Proportional
with Integral, Proportional with
Derivative with Anti-reset Windup and
ON/OFF

Rate
0 to 399.9 seconds

Reset
0 to 3999 seconds

PART 4
SPECIFICATIONS

Accuracy 0.03% reading

Resolution 10 / 1 µV

Temperature Stability 50 ppm/°C

NMRR 60 dB

CMRR 120 dB

A/D Conversion Dual slope

Reading Rate
3 samples per second

Digital Filter
Programmable

Display
4-digit, 9-segment LED
• 10.2 mm (0.40"): iS32, iS16, iS16D
(DualDisplay), iS8DV (Dual Vertical)
• 21 mm (0.83"): iS8
• 10.2 mm (0.40”) and 21 mm (0.83”):

iS8DH (Dual Horizontal)
red, green and amber programmable
colors for process variable, set point

Warm up to Rated Accuracy
30 min.

INPUT
Input Types
Analog Voltage, Analog Current

Voltage Input
0 to 100 mV
0 to 1 V (+100 mV),
0 to 10 Vdc

Input Impedance:
10 MΩ for 100 mV
1 MΩ for 1 V or 10 Vdc

Current Input
0 to 20 mA (5 ohm load)