Omega CNiS8DV User Manual

Page 41

Advertising
background image

37

ENTER OUTPUT 1 MENU:

Press

a

1) Press

a, if necessary, until CNFG prompt appears.

Press

d

2) Display advances to

INPT Input Menu.

Press

a

3) Press

a, if necessary, until display advances to OUT1 Output

1 Menu.

Press

d

4) Display advances to

SELF Self Submenu.

SELF SUBMENU:

The Self Option allows the output of the instrument to be controlled manually
from the front panel.

Press

d

5) Display flashes the current setting of Self,

ENBL Enabled or

DSBL Disabled.

Press

b

6) Press the

b button to select between Enable and Disable.

Press

d

7) If Self

ENBL Enabled was selected, display shows STRD

stored message momentarily and then advances to the next
menu (Output 1 setting is completed).

On the Run Mode display shows MXX.X The output is now
under the direct control of the operator and can be adjusted in
the Run Mode (M00.0 to M99.9), by pressing the

b and c

buttons, where M calls for manual (Self) control. For example,
setting of M50.0 of an analog output of 0 to 10 Vdc would
produce roughly 5 Vdc at the output.

8) If Self

DSBL Disabled was selected, display shows STRD

stored message momentarily and then advances to

ooLO

Minimum/Percent Low Submenu of Output 1 Menu.

There is a shorter way to Enable or Disable SELF Mode. From
a Run Mode press

d and then press a. SELF Mode is Enabled

now. Press

b or c to display MXX.X To Disable SELF press d

and then press

a. Display goes to the Run Mode. SELF Mode

is Disabled now.

MINIMUM/PERCENT LOW SUBMENU:

Specify in percent, the minimum value (0000) for control output. If the output is

analog proportional (Current or Voltage), then the minimum voltage or current, in

percent, is specified. If the output is time proportional (Relay, SSR or Pulse),

then the minimum duty-cycle, in percent, is specified.

Press

d

9) Display flashes 1st digit of previous “Percent Low” setting.

Press

b & c 10) Use b and c buttons to enter a new value for “Percent Low”.

Press

d

11) Display shows

STRD stored message momentarily and then

advances to

ooHI

Maximum/Percent High Submenu.