Omega CNiS8DV User Manual

Page 47

Advertising
background image

3.2.12 Output 2 Menu

Output 2 and Alarm 2 share the same contacts on the rear panel connector. If
Alarm 2 is Enabled, Output 2 is automatically Disabled.

Figure 3.10 Flow Chart for Output 2 Menu

ENTER OUTPUT 2 MENU:

Press

a

1) Press

a, if necessary, until CNFG prompt appears.

Press

d

2) Display advances to

INPT Input Menu.

Press

a

3) Press

a, if necessary, until Display advances to OUT2

Output 2 Menu.

Press

d

4) Display advances to

CTRL Control Type Submenu.

CONTROL TYPE SUBMENU:

Press

d

3) Display flashes

ON.OF On/Off, or PID PID.

Press

b

4) Scroll through the available selections: “ON.OF” or “PID”.

Press

d

5) Display shows

STRD stored message momentarily and then

advances to

AçTN only, if it was changed, otherwise press to

advance to

AçTN Action Type Submenu.

The ON.OF control is a coarse way of controlling the Process. The “Dead Band”
improves the cycling associated with the ON.OF control. The PID control is best
for processes where the set point is continuously changing and/or tight control of
the Process Variable is required.

43

It

is required that you put

the controller in the

Standby Mode for any

configuration change other

than Set Points & Alarms.