WIRING  

Step Six 

Wiring to a OMEGA ENGINEERING Controller 

LVCN‐120 Series Controller (4 or 20 mA output)

LVCN‐120 Shown 

 

Switching  Inductive  Loads:    The  use  of  suppressors  (snubbers)  is  strongly  recommended  when  switching 
inductive loads to prevent disrupting the microprocessor’s operation. The suppressors also prolong the life of 
the relay contacts. Suppression can be obtained with a catch diode for DC circuits and a resistor‐capacitor (RC) 
for AC circuits.   

 

Catch Diode

 Always use stepper relays between the sensor and external loads.  

For DC circuits use a catch diode such as 1N4148, shown on left. 

 

Refer to the following circuits for RC network assembly and installation:  

 

Choose R and C as follows:

 R: 0.5 to 1 Ohms for each volt across the contacts 
 C: 0.5 to 1 μF for each amp through closed contacts 

Notes: 

1. Use capacitors rated for 250 VAC. 
2. RC networks may affect load release time of solenoid loads. Check 

to confirm proper operation. 

3. Install the RC network at the meters relay screw terminals. An RC 

network may also be installed across the load. Experiment for best 
results. 

 

 

 