INSTALLATION  

Step Four 

OMEGA ENGINEERING's LVP‐51‐R level switch may be installed anywhere on a tank wall using the PE (LVP‐91) 
or PP (LVP‐92) bracket that the switch slides into.  The bracket comes with adhesive on the tank side that is 
sufficient  to  hold  the  sensor  in  position  temporarily  while  the  installation  is  tested,  but  for  permanent 
installation the bracket must be welded, glassed or strapped to the tank.  Extra brackets are available from 
OMEGA ENGINEERING, so that the level switch may be moved to different locations on the tank by sliding it 
into other brackets. 

Attach the bracket to the tank: 

1. Determine whether the tank is PP or PE. The slide‐in fitting shipped with the sensor is determined by 

the  part  number.  If  necessary,  obtain  an  additional 
bracket. 

2. Determine the mounting location for the level switch. The 

point  of  actuation  (where  the  sensor  will  send  a  “wet” 
signal) is most often at the center of the sensor; however 
the actual Point of Actuation (POA)  may differ depending 
on  the  application  liquid  and  tank  wall  characteristics.  
After  positioning  the  fitting  to  check  clearances,  etc., 
remove  the  paper  protective  strips  from  the  adhesive  of 
the bracket. 

3. Press the bracket into place. The adhesive provides a seal 

between  the  sensor  and  the  tank  wall,  and  will  hold  it  in 
place  during  testing  and  installation.    If  desired,  the  sensor  may  be  installed  temporarily  without 
welding  the  fitting  to  the  wall.    If  several  different  locations  must  be  tried  before  permanent 
installation, use double‐sided foam stick tape designed for PP or PE. 

4. After the sensor has been tested to verify the POA, weld, glass or strap the bracket to the tank using 

standard industrial plastic techniques.   

Special  note  for  small  round  tanks:    The  bracket  may  be  attached  to  small,  round  tanks,  as  long  as  the 
majority of the bracket is firmly attached to the wall.  However, extreme installations may affect the switches 
performance.   

Mount the sensor in the bracket: 

1. Slide the sensor into the bracket. 
2. After  trimming  the  sensor  wire  to  length  if  needed  by  the  installation,  thread  the  sensor  wire  into  a 

plastic flexible conduit with a 1/2" male fitting.  Screw the conduit into the sensor, being careful not to 
cross  the  threads.    Do  not  over  tighten  the  conduit  in  the  sensor  as  this  may  break  the  fitting.  Such 
damage  is  not  covered  by  the  warranty.    Take  care  while  pulling  the  wire  through  conduit  that  no 
excessive  tension  is  placed  on  the  sensor  end  of  the  wire,  so  that  the  wire  is  not  broken  from  the 
sensor housing. 

3. Connect  the  sensor  wire  to  the  controller  following  the  instructions  in  its  manual.  See  the  following 

Wiring Section for detailed wiring instructions. 

 