Omega Vehicle Security LVP-51 Series User Manual

Page 14

Advertising
background image

14 

MAINTENANCE 

 Step Seven 

Checking  the  Point  of  Actuation:    Raise  the  fluid  level  to  the  point 
where  the  sensor  sends  a  “wet”  signal  (Input  LED  will  turn  Amber  on 
OMEGA  ENGINEERING  controllers).    The  “dry”  signal  should  be  sent 
when  the  fluid  level  is  lowered  (Input  LED  will  turn  Green  on  OMEGA 
ENGINEERING  controllers).    The  actual  Point  of  Actuation  (POA) 
depends on many variables, including the thickness of the wall and the 
dielectric value of the liquid.  For example, thicker tank walls can raise 
the POA while thinner walls could lower the POA. 

If the POA needs to be changed, measure the distance and remount the 
sensor in a new location. 

Do not attempt to change the Point of Actuation by intentional 
miscalibration. 

 
If the sensor does not signal wet and dry reliably, it may be that: 

 the dielectric constant of the application fluid is too low 
 the tank wall is too thick for the application fluid 
 there are static or other electrical charges in the fluid 
 metal objects are within 6" of the sensor 
 calibration was performed incorrectly 

Try the calibration procedure again, after making corrections if possible.  If the full and empty states are too 
similar dielectrically, it may not be possible to use a capacitance sensor. 

Testing the Sensor: 

1. Power: Apply power to sensor, by connecting power to the controller and/or power supply. 
2. Full condition: Fill the  tank with the application liquid, by  filling the tank up to the sensor’s point of 

actuation. 

3. Test: With the sensor being fluctuated between wet and dry states, use a multimeter to ensure that 

the  correct  signals  are  being  produced  by  the  LVP‐51‐R  level  switch,  or  observe  the  sensor  indicator 
light in the controller. 

4. Point  of  Actuation:  Observe  the  point  at  which  the  rising  or  falling  fluid  level  causes  the  sensor  to 

change state, and move the installation of the sensor if necessary. 

Maintenance:  The LVP‐51‐R level switch itself requires no periodic maintenance except cleaning as required. 
However,  periodically  clean  any  coating  or  scaling  on  the  tank  wall  the  sensor  is  attached  to  and  check  the 
calibration.  It is the responsibility of the user to determine the appropriate maintenance schedule, based on 
the specific characteristics of the application liquids.  In addition, any dripping or condensation between the 
sensor and the tank wall fitting may need to be periodically cleaned to maintain accuracy. 
 
 

 

Advertising