CALIBRATION 

 Step Seven 

After it is installed in place, the must be calibrated by the user before operation.  Everything needed for the 
procedure  is  self‐contained  within  the  electronics  of  the  LVP‐51‐R  level  switch.  Two  dielectric  states—full 
condition  and  empty  condition—are  measured  by  the  LVP‐51‐R,  and  then  averaged  to  set  the  threshold 
between “wet” and “dry” at the sensor.  The empty state must be at least 6" below the bottom of the sensor 
for  calibration.    The  full  state  must  be  to  the  top  of  the  sensor  (not  just  to  the  point  of  actuation)  for 
calibration.    The  actual  application  fluid  at  its  intended  operating  temperature  must  be  used  during 
calibration.  Use the following procedure assumes that the sensor has already been wired to a power supply. 

1. Remove the cap from the sensor body by loosening the two screws located below the sensor.  Do not 

remove the screws from the sensor. Insert a small screwdriver into the small slot at the edge of the cap 
and gently pry upwards. 

2. Looking down you will see a small three‐position switch and two trim pots marked Full and Empty. You 

may start with whatever state the tank is in. 

3. Full  state:  With  the  tank  filled  to  the  top  of  the  sensor,  set 

the switch to the Full position (right).  Make sure your hands 
or  any  other  objects  are  not  touching  the  sensor  while 
calibrating  because  this  will  cause  a  false  reading.    Using  a 
small  nonmetallic  screwdriver  or  alignment  tool,  turn  trim 
pot  Full  until  the  LED  just  lights,  and  no  farther.    Note  the 
position. Now turn the trim pot back until the LED turns off.  
The  ideal  setting  for  the  trim  pot  is  midway  between  these 
on and off points. 

4. Empty state: With the tank drained to a point no closer than 6 inches below the bottom of the sensor, 

set the switch to the Empty position (left).  Set the Empty trim pot as in Step 3.   

5. After completing calibration, make sure to return the switch to the center position. Snap the cap back 

on by pressing down, and tighten the two screws. 

 

 

 

 