Flex vent – Quadra-Fire QV32-A User Manual

Page 13

Advertising
background image

17

STRAIGHT UP

VERTICAL VENTING

V (FT.)

45' MAX. (13.7m)

Figure 10. Straight up Vertical Venting

Use SL D-Series

components only.

NOTE: For vertical venting
over 20 feet a restrictor plate
is recommended for improved
flame appearance.

STRAIGHT OUT HORIZONTAL VENTING

H

Max. Run

36" (914 mm)

Use D-Series

components

only.

Figure 11. Straight Out Horizontal Venting

Note: Use two 90

o

elbows for corner

installations.

Figure 9.

Flex Vent

The flex vent must be supported with the spacing between
support intervals not exceeding 4 feet, with no more than ½
inch sag between supports.

A support is required at each change in venting direction,
and in any location where it is necessary to maintain the
necessary clearance to combustibles. A simple “up and out”
installation (Figure 9) requires only enough support to main-
tain the necessary clearance to combustibles. However, the
vent attachment point and the firestop location are consid-
ered to be supports.

3” CLEARANCE

TERMINATION

CAP

FLEX-VENT

1”

CLEARANCE

Note: There MUST be a 25% reduction
in total H when using flex vent, except
when using the simple up and out
installation (see Figure 9).

H

90-DEGREE

ELBOWS

Advertising
This manual is related to the following products: