For Vertical Runs - One ceiling firestop is REQUIRED at
the hole in each ceiling through which the vent passes.

To install firestops for vertical runs that pass through ceilings:

• Position a plumb bob directly over the center of the verti-

cal vent component.

• Mark the ceiling to establish the centerpoint of the vent.

• Drill a hole or drive a nail through this centerpoint.

• Check the floor above for any obstructions, such as wir-

ing or plumbing runs.

• Reposition the fireplace and vent system, if necessary,

to accommodate the ceiling joists and/or obstructions.

• Cut an 11-inch X 11-inch (280mm X 280mm) for D-Series

or a 10-inch X 10-inch (254mm X 254mm) hole through
the ceiling, using the centerpoint previously marked.

• Frame the hole with framing lumber the same size as the

ceiling joists.

Figure 28. Ceiling Firestop (Ceiling Side)

If the area above the ceiling is NOT an attic, position and
secure the ceiling firestop on the ceiling side of the previously
cut and framed hole.

Figure 27. Hole & New Framing Members

If the area above the ceiling IS an attic, position and secure
the firestop on top of the previously framed hole.

NOTE: Keep insulation away from the vent pipe at least
1 inch (25mm).

Figure 29. Attic Firestop

JOIST

CEILING FIRESTOP

CEILING

NAILS (4 REQUIRED)

CEILING

CEILING FIRESTOP

RAFTER

NAILS (4 REQUIRED)

CEILING

NEW
FRAMING
MEMBERS

EXISTING CEILING
JOISTS

CHIMNEY
HOLE

11" (280 mm) or
10" (254 mm)

11" (280mm) or
10" (254mm)

NOTE: There must be NO INSULATION or other combus-
tibles inside the framed firestop opening.