Quadra-Fire QV32-A User Manual

Page 19

Advertising
background image

23

Figure 18. Venting with three 90° elbows

Use SL D-Series

components only.

VENTING WITH THREE (3) 90

o

ELBOWS NATURAL GAS

VENTING WITH THREE (3) 90

o

ELBOWS PROPANE

V + H + V

1

+ H

1

MAX. = 40 FT (12.2m)

V + H + V

1

+ H

1

MAX. = 40 FT (12.2m)

V (MIN.)

H (MAX.)

H + H

1

(MAX.)

90

o

Elbow on Top

2 FT (610mm)

4 FT (1.22m)

1 FT (305mm)

3 FT (914mm)

6 FT (1.86m)

2 FT (610mm)

4 FT (1.22m)

8 FT (2.48m)

3 FT (914mm)

6 FT (1.86m)

12 FT (3.72m)

4 FT (1.22m)

8 FT (2.48m)

16 FT (4.8m)

5 FT (1.52m)

16 FT (4.8m)

16 FT (4.8m)

V (MIN.)

H (MAX.)

H + H

1

(MAX.)

90

o

Elbow on Top

NOT ALLOWED

NOT ALLOWED

1 FT (305mm)

2 FT (610mm)

4 FT (1.22m)

2 FT (610mm)

4 FT (1.22m)

8 FT (2.48m)

3 FT (914mm)

6 FT (1.86m)

12 FT (3.72m)

4 FT (1.22m)

8 FT (2.48m)

16 FT (4.8m)

5 FT (1.52m)

16 FT (4.8m)

16 FT (4.8m)

H

1

H

V

1

V

Note: There MUST be a 25% reduction
in total H when using flex vent, except
when using the simple up and out
installation (see Figure 9).