Tdvdsn series direct vent gas fireplace, Vertical restrictor plate (33tdvdsn only), Vertical through-the-roof installation – Temco Tool 33TDVDSN User Manual

Page 18

Advertising
background image

18

TDVDSN Series Direct Vent Gas Fireplace

20007890

When installing the 33TDVDSN with a Vertical Through-
the-Roof configured flue system the restrictor plate,
(#10002495) supplied with the appliance MUST BE
FITTED TO THE APPLIANCE
at installation.
Install restrictor plate to firebox top using two (2)
screws.

Vertical Restrictor Plate

(33TDVDSN only)

The legs of

the restrictor

plate must

go up.

Fig. 31 Place restrictor with legs pointing up.

T265

33TDV

restrictor Plate

10/04

T265

Vertical Through-the-Roof Installation

1. Locate your fireplace.
2. Plumb to center of the (4” (102 mm) flue collar from

ceiling above and mark position.

3. Cut opening equal to 9³⁄₈” x 9³⁄₈” (240 x 240 mm).
4. Proceed to plumb for additional openings through

the roof. In all cases, the opening must provide a
minimum of 1” (25 mm) clearance to the vent pipe,
i.e., the hole must be at least 9³⁄₈” x 9³⁄₈” (240 x
240mm).

5. Place fireplace into position.
6. Place firestop(s) #7DVFS or Attic Insulation Shield

#7DVAIS into position and secure. (Fig. 32)

7. Install roof support (Fig. 33) and roof flashing making

sure upper flange of flashing is below the shingles.
(Fig. 34)

8. Install appropriate pipe sections until the venting is

above the flashing. (Fig. 34)

9. Install storm collar and seal around the pipe.
10. Add additional vent lengths for proper height. (Fig.

35)

11. Apply high temperature sealant to 4” and 7” collars.

CFM100a

Firestop-Vertical

11"

(279mm)

11"

(279mm)

Attic Insulation
Shield

Joist

Ceiling In-
stallation

Joist

Upper Floor

Firestop Spacer

Nails (4)

CFM100a

Fig. 32 Place firestop spacer(s) and secure.

TWL101a

Twist Lock Pipe

2/8/99 djt

#8 Sheet Metal Screws

(3 per joint)

Sealant

Storm Collar

TWL101a

Fig. 34 Roof flashing.

NOTE: If the vertical rise is greater than 16’, then RP
Kit 255, Fresh Air Baffle, must be installed on the unit.
(Not Supplied)

CFM110

Typical ceiling/roof support

10/90

Typical Roof Support

Application

Typical Ceiling Sup-

port Application

Fig. 33 Roof and ceiling supports.

CFM110