TDVDSN Series Direct Vent Gas Fireplace

20007890

Troubleshooting

NOTE: Before troubleshooting the gas control system, be sure external shut off is in the “ON” position.

WARNING: Before doing any gas control service work, remove glass front!

Problem

Possible Cause

Solution

No gas to main burner

Low gas pressure to

With the main burner functioning, adjust the inlet

the appliance.

pressure regulator to supply gas to the appliance

within

the design parameters of the appli-

ance

manufacturer. (Typically

7”NG, 11”LPG)

Gas line valve not in ON position.

Rotate OFF/ON gas line valve to the ON position.

Thermostat/wall switch

Thermostat not in ON position.

Turn thermostat ON, and adjust temperature

control to call for heat.

Defective thermostat or thermostat

Replace thermostat or wiring.

wiring.

Thermostat/wall switch

Defective wall switch.

Repeat the above troubleshooting items covered

under

will not cycle main “Defective ther-

mostat or

thermostat wiring”, except substitute

the words

“wall switch” where the word ther-

mostat appears

in the instructions.

Excessive wire resistance.

Make certain all connections are made using wire

of the

proper size.

Valve wired wrong.

Refer to wiring diagram on Page 25.

No spark when system is Check for 120V between black “hot” If 120V not present, check fuse or circuit breaker
turned to “ON” and reset line at control module and “white”

or repair wiring leading to fireplace.

cycle* has been

return at module.

completed.
Spark for six (6) seconds a. Check that gas is turned on

Turn gas on and/or purge system.

at Ignitor, but no ignition system purged.

of burner.

b. Check that tips of ignitor are

Position elecrodes so tips are directly above

directly above ports on main burner. burner ports and about 1/4” to 3/8” above

Spark is between electrodes and not burner.

from one electrode to burner

c. Check for 120V at each coil on the If 120V present, but gas valve does not click,

gas valve and listen for click

replace gas valve.

indicating gas valve is opening.

Spark for six (6) seconds Check for clean ground path between Clean, position according to wiring diagram and

electrode bracket and fireplace

repair defective electric connections. If all

chassis. Check wiring to wiring

electrical connections are clean and correct,

diagram label. Check for broken

replace module.

electrode on high-tension lead

attachment to module.

Main burner lights

a. Check thermostat if applicable.

Turn thermostat up to call for heat or replace.

normally and then goes

out.

b. Check high-tension lead and

Replace spark electrode assembly.

connector for shorts.

*NOTE: Module DS2070S_A has a five (5) minute lockout timer: If burner does not light wait for five (5) minutes be-
fore attempting to relight.