Time delay adjustment, Sensor adjustments – TRENDnet Series 300 User Manual

Page 11

Advertising
background image

SECTION 4 ADJUSTMENTS

4--1

Time Delay Adjustment

Standard time delays are set to customer specifications
(if none specified, standard factory settings are used).

To change a setting, follow procedure on page 4-2. Use
Table 4-1 as a guide to time delay values and their corre-
sponding adjustment DIP switch or potentiometer.

Table 4-1. Time Delay Settings

DESCRIPTION

LABELS

FACTORY

SETTING

ADJUSTMENT

RANGE

S3 DIP

SWITCH

ADJUSTMENT

POTENTIOMETER

Override Momentary

TD ES

3 seconds

1 second

Actuator 1 on

1

Override Momentary

Normal Source Outages

TD ES

3 seconds

3 seconds

Actuator 1 off

1

Transfer to Emergency

TIMER

0 minutes

0 to 5

P2

Transfer to Emergency

TIMER

N/E

0 minutes

(full ccw)

0 to 5

minutes

P2

Override Momentary

Emergency S. Outages

4 seconds

non-adjustable

Retransfer to Normal

TIMER

30 minutes

1 second to

P1

Retransfer to Normal

TIMER

E/N

30 minutes

(full cw)

1 second to

30 minutes

P1

Unloaded Running

(Engine Cooldown)

5 minutes

non-adjustable

Sensor Adjustments

Voltage and frequency sensor pickup and dropout points
are set to customer specifications (if none specified,
standard factory settings are used). To change a setting,
follow procedure on page 4–2. Use Tables 4-2 and 4–3 for
settings and corresponding DIP switch actuators.

Any change in these settings may affect the

normal operation of the automatic transfer

switch. This change could allow the load circuits

to remain connected to a low voltage source.

!

Table 4-2. Voltage and Frequency Settings. (

Shaded DIP switches are standard factory settings).

DESCRIPTION

LABELS

SETTING

% of nominal

S1 DIP

DESCRIPTION

LABELS

SETTING

FACT. SET

ADJ RANGE

S1 DIP

SWITCH

PU / N

Pickup

90 %

95 % *

Actuator 3 off

3

PU / N

Pickup

90 %

90 %

Actuator 3 on

3

90 % *

Actuator 1 off

Actuator 2 off

2

1

Normal Source Voltage

DO / N

D

t

85 %

85 %

Actuator 1 on

Actuator 2 off

2

1

DO / N

Dropout

85 %

80 %

Actuator 1 off

Actuator 2 on

2

1

70 %

Actuator 1 on

Actuator 2 on

2

1

Emergency Source

– –

Pickup

90 %

non-adjustable

Emergency Source

Voltage

– –

Dropout

75 %

non-adjustable

– –

– –

Pickup

95 %

non-adjustable

E

S

– –

Dropout

85 %

non-adjustable

– –

Emergency Source

Frequency

60 / 50

60 / 50 Hz

60 Hz

60 Hz

Actuator 4 off

4

q

y

60 / 50

Hz

60 / 50 Hz

60 Hz

50 Hz

Actuator 4 on

4

Voltage Phases

3 4 1 4

3 4 / 1 4

3 4

3 phase

Actuator 6 off

6

Voltage Phases

3 4 , 1 4

3 4 / 1 4

3 4

1 phase

Actuator 6 on

6

* If dropout voltage is set to 90%, the pickup voltage must be set to 95%.

Table 4-3. Transformer Voltage Adjust.

(Low setting shifts all voltage settings down 4.2%; for example, 240 V to 230 V, or 480 V to 460 V)

DESCRIPTION

LABELS

FACTORY SETTING

ADJUSTMENT

S3 DIP SWITCH

Voltage Adjust (4 2%)

LOW /

HI

LOW

Actuator 2 off

2

Voltage Adjust (4.2%)

LOW /

HI

HI

HI

Actuator 2 on

2

Advertising