SECTION 5 CONTROL FEATURES – ENGINE EXERCISERS

5--1

These timers periodically exercise the emergency engine-generator plant. They can be set to exercise with or without
load transfer, or they can be completely disabled. The engine-generator should be exercised under load once a week for a
minimum time period of 20 minutes, or follow the recommendations of the engine-generator set manufacturer. Refer to
page 4–2 for location of DIP switches, battery (provided), and jumper block in the controller.

BUILT–IN ENGINE EXERCISER

The engine exerciser included in ASCO Series 300
Automatic Transfer Switches provides a once a week
20–minute exercise period. It occurs immediately when
the SET ENGINE EXERCISER push button is pressed
(and held for at least 5 seconds), and then at the same time
weekly thereafter. A 9 volt alkaline battery (DuracellR
MN1604, EverreadyR 522, or PanasonicR 6AM6) is
furnished and installed in the controller to maintain the
setting. The battery jumper block must be shifted to the
ON position. See Figure 4–2 on page 4–2.
Fill in day and time set. Week Day ______ Time _______.

DIP Switch Settings

FUNCTION

S1 DIP

SWITCH

S2 DIP

SWITCH

Std. Timer

Enabled

Actuator

7 on

7

Actuator

5 on

5

Std. Timer

Disabled

Actuator

7 off

7

Actuator

5 on

5

Exercise

without

Load

Actuator

8 off

8

Exercise

with Load

Actuator

8 on

8

Shaded DIP switches are standard factory settings.

status light

If

Exerciser with Load is set,

transfers load to Emergency.

Press until light

FLASHES

If

Exercise with Load is set,

retransfers load to Normal,

then stops generator after

5 min. cooldown.

Press to cancel an

active exercise period

(stops generator).

Press and hold for 5 sec. or until status

light blinks rapidly to set exercise period

immediately and every week hereafter

(generator starts).

Figure 5-1. Operator panel pushbuttons and light.

Select below either Exercise without Load or Exercise with Load according to the setting of DIP switch S1, actuator 8. The
load transfers from the Normal source to Emergency source (generator) and back again if Exercise with Load is selected.

Exercise without Load, DIP Switch S1, Actuator 8 off

8

How to Set Built–In Timer

Step

Function

Explanation

Push Button

Status Light

1

SET ENGINE

EXERCISER

hold 5 sec.

blinks rapidly

FfFfFf

set exercise period

Exercise the generator now and

every week at this time hereafter.

2

release

blinks slowly

FffFff

exercise period now active

Generator starts and runs.

3

press

BYPASS

TIME DELAY

F

stays on

cancel active exercise period

Generator stops.

4

F

stays on

generator off

Exerciser enabled; repeats every 7 days.

Exercise with Load, DIP Switch S1, Actuator 8 on

8

How to Set Built–In Timer

Step

Function

Explanation

Push Button

Status Light

1

SET ENGINE

EXERCISER

hold 5 sec.

blinks rapidly

FfFfFf

set exercise period

Exercise the generator now and

every week at this time hereafter.

2

release

blinks slowly

FffFff

exercise period now active

Generator starts and runs;

the load transfers to Emergency.

3

press

BYPASS

TIME DELAY

blinks slowly

FffFff

cancel active exercise period

The load retransfers to Normal; then

generator runs for 5 minute cooldown

( light blinks slowly during cooldown ).

4

F

stays on

generator off

Exerciser enabled; repeats every 7 days.