CONTROL FEATURES (continued)

5--5

OPTIONAL STRIP HEATER (Accessory 44)

Accessory 44 Strip Heater is designed to keep ambient
temperatures within the Automatic Transfer Switch
enclosure at acceptable levels. This accessory consists of a
mounting bracket with strip heater, thermostat, and
terminal block. A transformer with fuses is included when
the power for the assembly is derived from voltages above
120 V ac. The 120 V ac customer powered assembly does
not include a transformer. This optional accessory is
available factory installed or in kit form.

Turn the thermostat’s dial to required setting as shown.

dial

turn counterclockwise

to lower temperature

turn clockwise

to raise temperature

thermostat

AVAILABLE KITS FROM ASCO

Controls

Description

Accessory

Kit

Programmable Engine Exerciser

11CD

K601111

Serial Communication Module

72A

K601110

Strip Heater – Accessory 44

Description

Accessory

Kit

120 volt

customer supplied voltage

(without transformer)

44A

K613127–001

208 – 480 volt

ATS derived voltage

(with transformer)

44G

K613127–002

380 volt

ATS derived voltage

(with transformer)

44G

K613127

550 – 600 volt

ATS derived voltage

(with transformer)

44G

K613127–003

Advertising