SECTION 1

INSTALLATION

1--1

ASCO Series 300 Automatic Transfer Switches (ATSs) are

Listed under Underwriters Laboratories UL 1008

Standard for Safety for Automatic Transfer Switches. All

control features are UL Component Recognized, which

assures that ASCO automatic transfer switches meet

OSHA Safety Requirements and will be acceptable to

electrical inspectors.
ASCO Series 300 Automatic Transfer Switches are suitable

for emergency and standby system applications. They meet

emergency system rating requirements as defined in

National Electrical Code (NEC) Article 700 and UL 1008.

Also, they are suitable for the requirements of NEC Article

517 – Health Care Facilities, NEC Article 701 – Legally

Required Standby Systems, NEC Article 702 – Optional

Standby Systems, NFPA 99 Health Care Facilities, and

NFPA 110 Emergency and Standby Power Systems.

Rating Label

Each automatic transfer switch contains a rating label to

define the loads and fault circuit withstand / closing ratings.

Refer to the label on the transfer switch for specific values.

Do not exceed the values on the rating label.

Exceeding the rating can cause personal injury

or serious equipment damage.

!

Series 300 Automatic Transfer Switches are factory wired

and tested. Installation requires skid removal then secur-
ing the enclosure to the supporting foundation.

Remove the Shipping Skid

Open the front door and remove the four lag screws (two in

front, two in rear) securing the enclosure to the wood skid.

Supporting Foundation

The supporting foundation for the enclosure must be level
and straight. Refer to the applicable enclosure outline

drawing included with the Series 300 for all mounting

details including door opening space.

If bottom cable entry is used, the foundation must be

prepared so that the conduit stubs are located correctly.

Refer to the enclosure outline drawing for specified area

and location. Provide cable bending space and clearance to
live metal parts. When a concrete floor is poured, use

interlocking conduit spacer caps or a wood or metal

template to maintain proper conduit alignment.

Mounting

Refer to the applicable enclosure outline drawing fur-

nished with this switch and mount the Series 300 according

to details and instructions shown on diagram.

Auxiliary Cable Box for 1000–2000 amp

An auxiliary cable box is required if the power cables do not
enter the enclosure directly adjacent to the terminal lugs

(for example, if all power cables enter the top or bottom).

Order ASCO part no. 609027 if needed.

Do not route the power cables along

the sides of the Transfer Switch.

!

Line Connections

Refer to the Wiring Diagram provided with your Series 300

ATS. All wiring must be made in accordance with the

National Electrical Code and local codes.

It is unnecessary to remove pole covers from the transfer
switch. If you do remove them, reinstall them carefully.

De–energize the conductors before making any

line or auxiliary circuitry connections. Be sure

that Normal and Emergency line connections

are in proper phase rotation. Place engine gen-

erator starting control in the OFF position. Make

sure engine generator is not in operation.

Testing Power Conductors

Do not connect the power conductors to the ASCO Series

300 transfer switch until they are tested. Installing power
cables in conduit, cable troughs and ceiling-suspended

hangers often requires considerable force. The pulling of

cables can damage insulation and stretch or break the

conductor’s strands. For this reason, after the cables are
pulled into position, and before they are connected, they

should be tested to verify that they are not defective or

have been damaged during installation.

Protect the automatic transfer switch from

construction grit and metal chips to prevent

malfunction or shortened life of the ATS.

!

Connecting Power Conductors

After the power cables have been tested, connect them to

the appropriate terminal lugs on the transfer switch as

shown on the wiring diagram provided with this Series 300.

Make sure the lugs provided are suitable for use with the
cables being installed. Standard terminal lugs are solder-

less screw type and will accept the wire sizes listed on the

drawings provided with the Series 300. Be careful when
stripping insulation from the cables; avoid nicking or

ringing the conductor. Remove surface oxides from cables

by cleaning with a wire brush. When aluminum cable is
used, apply joint compound to conductors. Tighten cable

lugs to the torque specified on rating label.