Adjustments, Continued), How to change a setting – TRENDnet Series 300 User Manual

Page 12

Advertising
background image

ADJUSTMENTS

(continued)

4--2

Do not make any setting changes

while the controller is energized.

!

How to Change a Setting

1. Prevent the transfer switch from operating by discon-

necting one source first, then the other, as follows:

a.

If the transfer switch is in the Normal position,
open the emergency source circuit breaker. Turn
the engine starting control to off. Then open the
normal source circuit breaker.

b.

If the transfer switch is in the Emergency
position, open the normal source circuit breaker.
Turn engine starting control to test or run. Then
open the emergency source circuit breaker.

2. Disconnect both harness plugs from controller by

squeezing the latches. Do not pull on the wires.

3. Remove cover from the controller by releasing latch

on right side with your thumb. See Figure 4-1.

4. Locate the appropriate adjustment potentiometer or

DIP switch for the setting that you want to change.
Refer to Table 4-1 and Table 4–2 on page 4-1 and
Figure 4-2, Figure 4–3, Figure 4–4 on page 4–2.

5. Use a small screwdriver to turn the potentiometer

clockwise to increase the time delay or counterclock-
wise to decrease it. See Figure 4-3.

6. Use a ball-point pen (or similar pointed tool) to slide

the switch actuators left or right so they match the il-
lustration next to the setting (left = off, right = on).
Recheck the setting. See Figure 4-4.

7. Install the cover on the controller by hooking it on

the left side and latching the right side.

8. Reconnect both harness plugs to the controller by

aligning and pressing straight in until latches click.

Close the enclosure door.

!

9. Close the enclosure door, then restore both sources:

a.

If the transfer switch is in the Normal position
first close the normal source circuit breaker,
then close the emergency source circuit breaker.

b.

If the transfer switch is in the Emergency
position, close the normal source circuit breaker.
The load will be automatically retransferred to
the normal source. Then close the emergency
source circuit breaker.

10. Turn the engine starting control to automatic.

thumb

latch

cover

hook on

left side

Figure 4-1. Controller cover latch.

9 volt

alkaline

battery

battery

on/off

jumper

retransfer

to normal

time delay

transfer to

emergency

time delay

harness

plugs

S3 DIP

switch

S1 DIP

switch

S2 DIP

switch

Figure 4-2. Location of potentiometers.

P1 or P2

potentiometer

clockwise to

increase

counterclockwise

to decrease

Figure 4-3. Changing time delay potentiometers.

DIP

switches

SW1

SW2

SW3

actuator

on

off

(8 on each DIP switch)

Figure 4-4. Setting DIP switch actuators.