Maintenance, Owner – Trane IntelliPak SCWG 020 User Manual

Page 109

Advertising
background image

SCXG-SVX01B-EN

109

Piping Components

Water Valves
Water valves have a stern packing nut. If
there is evidence of water leakage at the
valve stem, proceed as follows:
1. Remove actuator motor from support

plate. (Remove four mount bolts)

2. Remove shaft coupling.
3. Torque the packing nut to 10-ft.-lbs. of

torque.

4. Replace shaft coupling.
5. Replace actuator motor (reinstall the

four mount bolts).

Note: If it is necessary to remove the four
valve body bolts for valve cleaning or
service, torque to 45 ft-lb.

Flow Switch Maintenance
Flow switches have a magnet on the
vane assembly that attracts ferrous
particulate may build up on the magnet to
the point that the vane will wedge so that
it will not operate.

When the flow switch does not operate,
remove and replace it or disassemble
and clean it.

Cleaning the Flow Switch
If ferrous particulate contaminates tower
water, the ferrous particles will cling to
the magnet on the switch paddle
assembly. A buildup of the ferrous
particles over a period os time will cause
the paddle to stick and cease to function
properly.

To avoid this problem, remove the switch
and clean each time you clean the
condensers, or clean as needed to keep
the switch operational.

To clean the paddle assembly, remove it
following the procedure below:
1. Remove the switch from the unit.
2. The paddle assembly and wire retainer

Maintenance

clip holds the paddle assembly in the
switch body.

3. Remove the wire retainer clip by

reaching down past the paddle with a
pair of slim nosed pliers and gripping
the end of the wire. Pull up on the wire
clip and remove it.

4. After removing the wire clip, use the

pliers to pull the paddle assembly out of
the switch barrel. Clamp the pliers onto
the end of the paddle and remove the
paddle assembly. It will slide straight
out.

5. Clean the ferrous particulate from the

magnet using a rag or tack cloth. The
particulate is attracted to the magnet,
so it is necessary to pull it off. It will not
simply wipe off.

6. After cleaning the magnet, replace the

paddle assembly into the switch body’s
barrel. However, it is important to
position the paddle perpendicular to the
arrow on the switch’s side and place the
paddle’s flat side facing the opposite
direction or the arrow. Push the paddle
assembly in until it hits the barrel cavity
bottom.

7. Place the spring clip into the switch

barrel and push it down with a small,
flat blade screwdriver until the spring
clip engages the groove in the switch
barrel.

8. When replacing the paddle assembly,

check the operation by pushing on the
paddle’s flat side. The paddle should
swing freely in the direction of the
arrow. This action confirms that the
paddle assembly is properly installed.

9. Replace the switch into the unit piping

using a good pipe thread sealer. Tighten
the switch so that its final position has
the arrow parallel to the water pipe and
pointing toward the left end of the unit
(arrow is pointing in the direction of the
water flow).

Owner

Advertising