SCXG-SVX01B-EN

77

Owner

General
Information

Points List

RTM Module:

Binary inputs
• Emergency stop
• External auto/stop
• Unoccupied/occupied
• Dirty filter
• VAV changeover with hydronic heat

Binary outputs
• VAV box drive max (VAV units only)
• CV unoccupied mode indicator (CV units

only)

• Alarm
• Fan run request
• Water pump request (water-cooled

only)

Analog input
• Airside economizer damper minimum

position

Analog output
• Outside air damper actuator

Heat Module:
• Analog output

GBAS Module:

Binary inputs
• Demand limit contacts

Binary outputs
• Dirty filter relay
• Refrigeration fail relay
• Heat fail relay
• Supply fan fail relay
• Active diagnostics

Analog inputs
· Occupied zone cooling setpoint
· Occupied zone heating setpoint
· Unoccupied zone cooling setpoint
· Unoccupied zone heating setpoint or

minimum outside air flow setpoint

· Supply air cooling setpoint
· Supply air heating setpoint
· Supply air static pressure setpoint

ECEM Module:

Analog inputs
• Return air temperature
• Return air humidity

In addition, units with a VOM have:

Binary inputs
• VOM mode A, unit off
• VOM mode B, pressurize
• VOM mode C, exhaust
• VOM mode D, purge
• VOM mode E, purge w/duct pressure

control

Binary output
• V.O. relay

TCI Module:

Binary input
• Enthalpy enable airside economizer

Binary outputs
• Compressor on/off status
• Ventilation status
• Condenser water flow status
• Heat status

Analog outputs
• Supply air pressure
• Supply air temperature
• Suction temperature of each circuit
• Entering economizer water temperature
• Zone temperature
• Entering condenser water temperature
• Supply air temperature reset signal
• Morning warmup sensor temperature
• Entering air temperature

Analog inputs
• Cooling and heating setpoints
• VAV discharge air temperature

setpoints

• Supply air pressure setpoint
• Cooling and heating enable/disable
• Air economizer enable/disable
• Airside economizer minimum position
• Unit priority shutdown