Electrical
Requirements

Selection Procedures

RLA = Rated Load Amps
Compressor LRA = Locked Rotor Amps
Fan Motor LRA = Locked Rotor Amps,
N.E.C. Table 430 - 150
FLA = Full Load Amps, N.E.C.

Table 430 - 150

Voltage utilization range is ±10 percent

Determination of minimum circuit
ampacity (MCA).
MCA = 1.25 x largest motor amps/VFD
amps (FLA or RLA) + the sum of the
remaining motor amps.

Determination of maximum fuse size
(MFS) and maximum circuit breaker size
(MCB).
MFS and MCB = 2.25 x largest motor
amps (FLA or RLA) + the sum of the
remaining motor amps.

If the rating value determined does not
equal a standard current rating of over
current protective device, use the next
lower standard rating for the marked
maximum rating.

For units with the dual power option,
there are two circuits that need calcula-
tions using the formulas above:

circuit #1 - fans
circuit #2 - compressors

If the rating value determined does not
equal a standard current rating of over
current protective device, use the next
lower standard rating for the marked
maximum rating.

Installation

Table I-ER-2. SCWG/SIWG Compressor Motor Data

200V

460V

575V

HP

RLA

LRA

RLA

LRA

RLA

LRA

10

33.1

269

14.4

117

11.5

94

15

46.9

409

20.4

178

16.4

143

Table I-ER-3. SCRG/SIRG Compressor Motor Data

200V

460V

575V

HP

RLA

LRA

RLA

LRA

RLA

LRA

10

38.4

269

16.7

117

13.4

94

15

55.0

409

24.1

178

19.1

143

Table I-ER-4. Fan without VFD

200V

460V

575V

HP

FLA

LRA

FLA

LRA

FLA

LRA

5

16.1

105

6.7

46

5.4

37

7.5

25.0

152

10.8

66

8.2

54

10

32.9

193

14.2

84

11.4

66

15

44.8

290

20.3

126

16.2

102

20

61.0

373

25.0

162

20.0

132

25

74.0

469

31.0

204

24.2

162

Table I-ER-5. Fan with VFD

200V

460V

HP

FLA

LRA

FLA

LRA

7.5

29.0

152

14.3

66

10

38.3

193

18.2

84

15

42.7

290

25.3

126

20

55.2

373

32.0

162

25

67.8

469

32.7

204

Table I-ER-1. Number of Compressors per Unit

SCWG/SIWG 20

25

30

35

SCRG/SIRG

20

25

32

10 HP

2

2

1

-

15 HP

-

-

1

2

Table I-ER-6. Electric Heat - Single Stage

SCWG/SIWG

SCRG/SIRG

Heat

200V

460V

Size

Size

Kw

Amps

Amps

20

20

16

44.8

19.6

25

25

20

55.6

24.2

30

-

24

66.8

29.0

-

32

26

72.4

31.6

35

-

28

78

34.0

Note:
Electric heat amperage should not be considered when determining minimum circuit ampacity. The current of the
unit in the heating mode will not exceed the current of the unit in the cooling mode.