Owner general information – Trane IntelliPak SCWG 020 User Manual

Page 79

Advertising
background image

SCXG-SVX01B-EN

79

Table O-GI-2. RTM Sensor Resistance vs. Temperature

Temperature (F)

Resistance (ohms)

Temperature (F)

Resistance (ohms)

-40

346.1

71

11.60

-30

241.7

72

11.31

-20

170.1

73

11.03

-10

121.4

74

10.76

-5

103.0

75

10.50

0

87.56

76

10.25

5

74.65

77

10.00

10

63.8

78

9.76

15

54.66

79

6.53

20

46.94

80

9.30

25

40.40

85

8.25

30

34.85

90

7.33

35

30.18

100

5.82

40

26.22

105

5.21

45

22.85

110

4.66

50

19.96

120

3.76

55

17.47

130

3.05

60

15.33

140

2.50

65

13.49

150

2.05

66

13.15

160

1.69

67

12.82

170

1.40

68

12.50

180

1.17

69

12.19

190

0.985

70

11.89

200

0.830

Owner

General
Information

Table O-GI-4. RTM Resistance Value vs. System Operating Mode

Resistance
applied to RTM Mode

CV Units

VAV Units

input terminals (Ohms)

Fan Mode

System Mode

System Mode

2320

Auto

Off

Off

4870

Auto

Cool

7680

Auto

Auto

Auto

10,770

On

Off

13,320

On

Cool

16,130

On

Auto

19,480

Auto

Heat

27,930

On

Heat

Note: Mode boundaries are 1000 to 40,000 ohms. Other boundaries are equal to the midpoint between the
nominal mode resistance.

Table O-GI-3. RTM Setpoint Analog Inputs

Cooling or Heating Setpoint Input (F)

Cooling Setpoint Input (F)

(using RTM as zone temp. source)

(using RTM as supply air temp. source)

Resistance (ohms)

40

40

1084

45

45

992

50

50

899

55

55

796

60

60

695

65

65

597

70

70

500

75

75

403

80

80

305

NA

85

208

NA

90

111

Occupied/Unoccupied Contacts
To provide night setback control if a
remote panel

with night setback was not

ordered, install a field-supplied contact.
This binary input provides the building’s
occupied/unoccupied status to the RTM. It
can be initiated by a time clock, or a
building automation system control
output. The relay’s contacts must be rated
for 12 ma @ 24 VDC minimum. Refer to
the appropriate wiring diagrams
(attached to the unit control panel for the
proper connection terminals in the unit
control panel.

Emergency Stop Input
A binary input is provided on the RTM
board for installation of a field-supplied
normally closed (N.C.) switch to use
during emergency situations to shut
down all unit operations. When open, an
immediate shutdown occurs. An
emergency stop diagnostic enters the
human interface and the unit will require
a manual reset. Refer to the unit wiring
diagrams (attached to the unit control
panel for the proper connection
terminals. The switch must be rated for
12 ma @ 24 VDC minimum. This input
will override all VOM inputs, if the VOM
option is on the unit.

VAV Box Option
To interlock VAV box operation with
evaporator fan and heat/cool modes,
wire the VAV boxes/air valves to VAV box
control connections on the terminal block.

Supply Duct Static Pressure Control
The RTM relies on input from the duct
pressure transducer when a unit is
equipped with IGV or VFD to position the
IGV or set the supply fan speed to
maintain the supply duct static pressure
to within the static pressure setpoint
deadband.

RTM Sensors
RTM sensors include: zone sensors with
or without setpoint inputs and modes,
supply air sensor, duct static pressure,
outside air temperature, outside air
humidity, airflow proving, and dirty filter.