Specifications of electrical parts, 1. indoor unit, 2. outdoor unit – Toshiba RAV-SM1101BT-E User Manual

Page 23

Advertising
background image

21

6. SPECIFICATIONS OF ELECTRICAL PARTS

6-1. Indoor Unit

RAV-SM561BT-E / SM801BT-E / SM1101BT-E / SM1401BT-E

No.

1

2

3

4

5

6

7

8

Parts name

Fan motor (SM801BT-E)

Fan motor
(SM561BT-E/SM1101BT-E/SM1401BT-E)

Thermo. sensor (TA-sensor)

Heat exchanger sensor (TCJ-sensor)

Heat exchanger sensor (TC-sensor)

Float switch

Drain pump motor

Reactor

Type

ICF-280-120-1

ICF-280-120-2

258 mm

Ø6 mm, 1200 mm

Ø6 mm, 1200 mm

FS-0218-106

ADP-1406

CH-43-2Z-K

Specifications

Output (Rated) 120 W, 220–240 V

Output (Rated) 120 W, 220–240 V

10 k

at 25°C

10 k

at 25°C

10 k

at 25°C

10 mH, 1 A

6-2. Outdoor Unit

RAV-SM560AT-E

No.

1

2

3

4

5

6

7

8

9

10

11

Parts name

Fan motor

Compressor

Reactor

Outdoor temp. sensor (To-sensor)

Heat exchanger sensor (Te-sensor)

Suction temp. sensor (Ts-sensor)

Discharge temp. sensor (Td-sensor)

Fuse (Switching power (Protect))

Fuse (Inverter, input (Current protect)

4-way valve solenoid coil

Compressor thermo. (Protection)

Type

ICF-140-43-1

DA130A1F-23F

CH-57

STF-0108G

US-622

Specifications

Output (Rated) 40 W

3 phase, 4P, 1100 W

10 mH, 16A

10 k

at 25°C

10 k

at 25°C

10 k

at 25°C

50 k

at 25°C

T3.15 A, AC 250 V

25 A, AC 250 V

ON : 90 ± 5°C, OFF : 125 ± 4°C

RAV-SM800AT-E

No.

1

2

3

4

5

6

7

8

9

10

11

Parts name

Fan motor

Compressor

Reactor

Outdoor temp. sensor (To-sensor)

Heat exchanger sensor (Te-sensor)

Suction temp. sensor (Ts-sensor)

Discharge temp. sensor (Td-sensor)

Fuse (Switching power (Protect))

Fuse (Inverter, input (Current protect))

4-way valve solenoid coil

Compressor thermo. (Protection)

Type

ICF-140-63-1 or ICF-140-63-2

DA220A2F-20L

CH-47

DKV-M0ZS743B0

US-622

Specifications

Output (Rated) 63 W

3 phase, 4P, 1600 W

8 mH, 16 A

10 k

at 25°C

10 k

at 25°C

10 k

at 25°C

50 k

at 25°C

T3.15 A, AC 250 V

25 A, AC 250 V

ON : 90 ± 5°C, OFF : 125 ± 4°C