* Connector of RAV-SM560AT-E differs

from that of RAV-SM800AT-E,
RAV-SM1100AT-E, RAV-SM1400AT-E.

CN300: Motor coil winding
CN301: Motor position detection

Are connections of CN301 and

CN300 of P.C. board correct?

Does the fan rotate without trouble

when handling the fan with hands under condition

of removing CN301 and CN300 from P.C. board?

The status that the resistance values

between leads below are 50 to 80

for 40 motor (ICF-140-40) and 25 to 55

for 60 motor (ICF-140-60-1) is normal.

Between (Red lead) and (White lead)

Between (White lead) and (Black lead)

Between (Black lead) and (Red lead)

of motor winding of connector (CN301)

The status that there is

5k to 20k resistance values between

(Yellow lead) and (Pink lead)

of motor position detection of

connector (CN300) is normal.

Normal fan motor
(Control or CDB P.C. board)

Defective fan motor

NOTE :
However, GND circuit error inside of the motor is rarely detected even if the above check is carried out.
When the circuit does not become normal even if P.C. board has been replaced, replace outdoor fan motor.

Objective P.C. board

Fan motor winding

Motor position detection

Fan motor winding

Motor position detection

Single phase

RAV-SM560AT-E

Single phase

RAV-SM800AT-E

Control P.C. board

CN300

CN301

——

——

CDB P.C. board

CN301

CN300

——

——

Single phase

RAV-SM1100AT-E, SM1400AT-E

CDB P.C. board

CN301

CN300

CN303

CN302

1

2

2

3

3

1

1

4

(Control P.C. board or CDB P.C. board)

NO

NO

NO

YES

YES

YES

YES

CN301

CN300

[P22 error]/[1A error]