8-4. Indoor P.C. Board Optional Connector Specifications

Function

Option output

Outside error
input

Filter option
error

CHK
Operation check

DISP display
mode

EXCT demand

Connector

No.

CN60

CN80

CN70

CN71

CN72

CN73

Pin
No.

1

2

3

4

5

6

1

2

3

1

2

1

2

1

2

1

2

Specifications

DC12V (COM)

Defrost output

Thermo. ON output

Cooling output

Heating output

Fan output

DC12V (COM)

DC12V (COM)

Outside error input

Filter/Option/Humidifier
setup input

0V

Check mode input

0V

Display mode input

0V

Demand input

0V

Remarks

ON during defrost operation of outdoor unit

ON during Real thermo-ON (Comp ON)

ON when operation mode is in cooling system
(COOL, DRY, COOL in AUTO cooling/heating)

ON when operation mode is in heating system
(HEAT, HEAT in AUTO cooling/heating)

ON during indoor fan ON
(Air purifier is used/Interlock cable)

(When continued for 1 minute)
Check code “L30” is output and forced operation stops.

Option error input is controlled. (Protective operation
for device attached to outside is displayed.)

* Setting of option error input is performed from

remote controller. (DN=2A)

Used for operation check of indoor unit. (Communica-
tion with outdoor unit or remote controller is not
performed, but the specified operation such as indoor
fan “H” or drain pump ON is output.)

Display mode enables indoor unit and remote control-
ler to communicate. (When power is turned on)

Forced thermo-OFF operation in indoor unit