1) Adjustment range Remote controller setup tem-

perature (°C)

Wired type

COOL/

DRY

18 to 29

Heating

operation

18 to 29

Auto

operation

18 to 29

2) Using the item code 06, the setup temperature in

heating operation can be compensated.

Setup data

Setup temp.
compensation

0

2

4

6

+0°C

+2°C

+4°C

+6°C

Setting at shipment

Setup data

2

1) Based on the difference between Ta and Ts, the

operation frequency is instructed to the outdoor unit.

1) Operation with (HH), (H), (L), or [AUTO] mode is

performed by the command from the remote controller.

2) When the air speed mode [AUTO] is selected, the air

speed varies by the difference between Ta and Ts.

<COOL>

• Controlling operation in case when thermo of remote

controller works is same as a case when thermo of
the body works.

• If the air speed has been changed once, it is not

changed for 3 minutes. However when the air volume
is exchanged, the air speed changes.

• When cooling operation has started, the air speed

selects a downward slope, that is, the high position.

• If the temperature is just on the difference boundary,

the air speed does not change.

• Mode in the parentheses indicates one in automatic

cooling operation.

Remarks

Shift of suction tempera-
ture in heating operation

HH > H > L > LL