Toshiba RAV-SM1101BT-E User Manual

Page 82

Advertising
background image

80

Remote
controller

Central
control
remote
controller

Indoor unit

Indoor

unit

Network

adapter

Indoor

control

P.C. board

X Y

A B

Indoor

control

P.C. board

A B

Indoor

unit

Indoor

control

P.C. board

A B

Indoor

unit

Indoor

control

P.C. board

A B

Indoor unit

Indoor

unit

Network

adapter

Indoor

control

P.C. board

X Y

A B

Indoor

control

P.C. board

A B

Connectable indoor units per group: Up to 8 units
(1-remote controller system*)
* In case of 2-remote controllers system,
the connectable indoor units are up to 7 units.

12-2-5. Communication Cable Specifications

12-2-6. Cable Connection

<Network cable connection>

• Install a network adapter per 1 group of the group control (including single unit control). Also install a network

adapter to one of the indoor units in the group control.

No.

1

2

Communication circuit

Remote controller
communication side

AI NET side

Communication cable specifications

Cable

Cable type

Cable dia.

Cable length

Cable

Cable type

Cable dia.

Cable length

Neutral 2-cable type

CVV

(JIS C3401) Controlling vinyl insulation vinyl seal cable

VCTF (JIS C3306) Vinyl cab tire round type cord
VCT

(JIS C3401) 600V vinyl cab tire cable

VVR

(JIS C3401) Vinyl insulation seal cable round type

MVVS Cable with net shielding for instrumentation
CPEVS Shielded polyethylene insulation vinyl seal cable

0.5 to 2.0 mm²

Total cable length Max. 500m
(Up to 400m when there is wireless remote controller in group)

Neutral 2-cable type

MVVS Cable with net shielding for instrumentation

1.25 mm²

500 m, 2.0 mm²

1 km

Total cable length : Up to 500m when using 1.25mm² cable,

Up to 1000m when using 2.0mm² cable