8-2. Control Specifications

No.

1

2

Item

When power
supply is reset

Operation mode
selection

Outline of specifications

1) Distinction of outdoor units

When the power supply is reset, the outdoors are
distinguished, and control is exchanged according to
the distinguished result.

2) Based on EEPROM data, speed of the indoor fan or

setting whether to adjust air direction or not is se-
lected.

1) Based on the operation mode selecting command

from the remote controller, the operation mode is
selected.

Remote controller

command

STOP

FAN

COOL

DRY

HEAT

AUTO

Outline of control

Air conditioner stops.

Fan operation

Cooling operation

Dry operation

Heating operation

• COOL/HEAT operation mode

is automatically selected by Ta
and Ts for operation.

1) Judge the selection of COOL/HEAT mode as shown

in the figure above.

When 10 minutes passed after thermostat had
been turned off, the heating operation (Thermo
OFF) is exchanged to cooling operation if Tsh
exceeds +1.5 or more.

(COOL OFF) and (COOL ON) in the figure indicate
an example.

When 10 minutes passed after thermostat had
been turned off, the cooling operation (Thermo
OFF) is exchanged to heating operation if Tsc
exceeds –1.5 or less.

2) For the automatic capacity control after judgment of

COOL/HEAT, refer to item 4.

3) For the temperature correction of room temperature

control in automatic heating operation, refer to item 3.

Remarks

Air speed/
Air direction adjustment

Ta : Room temperature
Ts : Setup temperature

Tsc : Setup temperature in

cooling operation

Tsh : Setup temperature

+ Room temperature
control temperature
compensation