Filter installation, Supply fan adjustment, Installation – Trane Voyager 1 Rooftop Unit TSD User Manual

Page 14

Advertising
background image

Installation

RT-SVX20A-E4

14

Filter installation

To gain access to filters, remove the
supply fan access panel on
downflow units and the filter access
panel on the end for horizontal
units.

Number and size of filters is
determined by size and
configuration of the unit. If
disposable filters were chosen as an
option, they are shipped in the
supply fan section.

CAUTION! Do not operate unit
without filters in place.

The maximum pressure drops
allowable on filters are:

EU2/G2: 120 Pa

EU4/G4: 150 Pa

Table 7 - Filter arrangement

Unit

EU2/G2

EU4/G4

Quantity

Size

Quantity

Size

TSD/TSH/YSD/YSH/WSD/WSH 060

2

(508x762x25)

2

(500x750x25)

TSD/TSH/YSD/YSH/WSD/WSH 072

4

(406x635x50)

4

(395x625x50)

TSD/TSH/YSD/YSH/WSD/WSH 090

4

(406x635x50)

4

(395x625x50)

TSD/TSH/YSD/YSH 102

4

(508x635x50)

4

(500x625x50)

TSD/TSH/YSD/YSH 120

4

(508x635x50)

4

(500x625x50)

Supply fan adjustment

Use the following procedure to
determine the proper adjustment of
the supply fan for a specific
application.
1. Determine total external static

pressure about system and
accessories.

• Obtain the design airflow rate

and the design external static
pressure drop through the
distribution system.

• Add static pressure drop of the

accessories installed on the unit.
(Table 9)

• Add the total accessory static

pressure drop (from step 1b) to
the design external static
pressure (from step 1a). The sum
of these two values is the total
system external static pressure.

2. Using the Tables 10 through 35 to

find the external static pressure
that most closely approximates
total system external static
pressure. Then locate the
appropriate airflow rate for your
unit. The value obtained
represents the brake horsepower
for the supply fan motor and the
fan RPM.

3. Adjust motor sheave according

to Table 8.