Fire thermostat, Controls – Trane Voyager 1 Rooftop Unit TSD User Manual

Page 40

Advertising
background image

Controls

RT-SVX20A-E4

40

Fire thermostat

There are two sensors in the fire
thermostat Kit: Sensor X13100040-
01 is factory-set to open at 57°C,
Sensor X13100040-02 is set to open
at 115°C.

Sensors are mounted directly in the
ductwork. They should be installed
where elements can respond
quickly to air temperature changes.
If not possible, the sensor may be
installed on a suitable bracket so
the air is drawn across the element.
Sensor X13100040-01 has to be
mounted in the return air duct.
Sensor X13100040-02 has to be
mounted in the supply air duct.

Note: Do not permit element guard
to touch internal parts. Do not
locate sensor where the air
circulation is restricted by baffles.

At the selected location, cut a hole
to clear element guard and drill
holes for mounting screws
according to Figure 23. Connect
wires according to Figure 24.

Figure 23 - Duct mounting of fire
thermostat

1 = Fire thermostat
2 = Hole in the duct

Figure 24 - Connection of fire thermostat
with TCI board

1 = Field-supplied emergency stop

device

2 = Remove factory-supplied jumper

1

2