Controls

RT-SVX20A-E4

36

Wiring the wall-mounted CO

2

sensor

DVC setpoint potentiometer on
economizer module can be adjusted
as follows:

0% - 500ppm, 50% - 1000 ppm,

100% - 1500ppm

The outside air damper will
modulate from minimum position
setting to up to 100% while
attempting to maintain the CO

2

setpoint.

Wiring the duct-mounted CO

2

sensor
1. Connect the common wire from

the controller to the ground
terminal (terminal 0) (Figure 16).

2. For voltage output, connect the

signal wire to terminal V.

3. Connect the power according to

the guidelines in Power supply
requirements.

Figure 15 - Wall-mounted CO

2

sensor wiring

Figure 16 - Terminal connections and LED locations

1 = Outer jumper
2 = Power terminal
3 = Ground terminal
4 = Output terminals

1

2

3

4