Installation

31

RT-SVX20A-E4

The "ABC" indicator on the face of
the phase indicator will glow if
phase is ABC for terminals L1, L2,
L3.

IMPORTANT! After completion of
wiring, check all electrical
connections, and ensure all
connections are tight. Replace and
secure all electrical box covers and
access doors before leaving unit or
connecting power to circuit
supplying the unit.

CAUTION! Units with scroll
compressors are not equipped with
crankcase heaters.

WARNING! Disconnect all power,
including remote disconnects, and
discharge all capacitors before
servicing.

Follow proper lockout/tagout
procedures to ensure the power
cannot be inadvertently energized.
After power is removed, allow
4 minutes for capacitors to
discharge. Verify with an
appropriate voltmeter that all
capacitors have discharged. Failure
to disconnect power and/or
discharge capacitors before
servicing could result in death or
serious injury. For additional
information regarding the safe
discharge of capacitors, see Trane
Service Bulletin PROD-SVB06A.

Table 36 - Unit wiring

Standard Supply Fan Motor

Oversized Supply Fan Motor

Unit Model
and size

Main power

supply

(V/Ph/Hz)

Minimum Circuit

Ampacity

(A)

Maximum Overcurrent

Protective Device (Fuse

or Circuit Breaker)

(A)

Minimum circuit

ampacity

(A)

Maximum Overcurrent

Protective Device (Fuse

or Circuit Breaker)

(A)

Without Electric heat option

TSD/TSH 060

400/3/50

18,2

32

19,3

32

TSD/TSH 072

400/3/50

24,4

32

25,5

32

TSD/TSH 090

400/3/50

26,2

40

27,2

40

TSD/TSH 102

400/3/50

28,3

40

29,3

40

TSD/TSH 120

400/3/50

32,6

40

32,6

40

YSD/YSH 060

400/3/50

18,2

32

-

-

YSD/YSH 072

400/3/50

24,4

32

25,5

32

YSD/YSH 090

400/3/50

26,2

40

27,2

40

YSD/YSH 102

400/3/50

28,3

40

29,3

40

YSD/YSH 120

400/3/50

32,6

40

32,6

40

WSD/WSH 060

400/3/50

20,1

32

21,2

32

WSD/WSH 072

400/3/50

23,1

32

24,2

32

WSD/WSH 090

400/3/50

26,2

40

27,2

40

With Electric heat

TSD/TSH 060

400/3/50

26,4

50

27,5

50

TSD/TSH 072

400/3/50

37,8

50

38,9

50

TSD/TSH 090

400/3/50

39,2

50

40,2

50

TSD/TSH 102

400/3/50

50,1

63

51,1

63

TSD/TSH 120

400/3/50

51,8

63

51,8

63

WSD/WSH 060

400/3/50

40,8

50

41,9

50

WSD/WSH 072

400/3/50

55,2

63

56,3

63

WSD/WSH 090

400/3/50

58,3

63

59,3

63

Advertising