Sensors 35, Controls, Sensors – Trane Voyager 1 Rooftop Unit TSD User Manual

Page 35

Advertising
background image

Controls

35

RT-SVX20A-E4

The CO

2

sensor is designed to

operate with a nominal 24 Vac
supply. The power supply should
maintain the voltage between 20 to
26 Vac.

Table 41 - CO

2

sensor wire size

Wire size

(mm²)

Maximum

wire lengh

(m)

0,25

50

0,5

100

1

200

Table 40 - Specifications

Wall-mounted Duct-mounted

Measuring range CO

2

0-2000 ppm

Accuracy at 25°C

< +/- [40 ppm CO

2

+ 3% of

reading]

(included repeatability and

calibration uncertainty)

< +/- [30 ppm CO

2

+ 2% of

reading]

(included repeatability and

calibration uncertainty)

Non-linearity

< 1.0% full scale

Temperature dependence of output

0.3% full scale/°C

Long-term stability

< 5.0% full scale/ 5 years

Recommended calibration interval

5 years

Response time

1 minute (0-63%)

Operating temperature

15-35°C

-5-45°C

Storage temperature

-20-70°C

Humidity range

0-85% relative humidity

Airflow range

0-10 m/s)

Output signals (jumper selectable)

0-10 Vdc

Resolution of analog outputs

10 ppm CO

2

Recommended external load

Current output: max 500

Voltage output: min. 1000

Power supply

Nominal 24 Vac

Power consumption

< 5 VA

Warm-up time

< 15 minutes

Dimensions (mm)

108 x 80 x 36

80 x 80 x 200

CO

2

sensors

Wall-mounted and duct-mounted
CO

2

sensors

Power supply requirements

CAUTION! Make sure that you
connect the power wire only to the
24V terminal. Connecting the power
wire to the output terminal may
result in equipment damage.