General data, General data (3, 4 ton) – Trane PKGP-PRC003-EN User Manual

Page 14

Advertising
background image

14

PKGP-PRC003-EN

General
Data

(3, 4 Ton)

Table GD-1 — General Data

3 Ton Convertible Units

4 Ton Convertible Units

WSC036A1

WSC036A3,A4,AW

WSC048A1

WSC048A3,A4,AW

Cooling Performance

1

Gross Cooling Capacity

38,100

38,100

50,800

50,800

SEER

2

9.80

10.20

10.50

10.70

Nominal CFM / ARI Rated CFM

1,200 / 1,200

1,200 / 1,200

1,600 / 1,600

1,600 / 1,600

ARI Net Cooling Capacity

36,600

36,000

48,500

48,500

Integrated Part Load Value

System Power (KW)

4.09

3.96

5.16

5.05

Heating Performance

1

High Temp. Btuh Rating

35,000

35,000

47,000

47,000

System Power KW

3.46

3.35

4.68

4.53

Low Temp. Btuh Rating

18,600

18,600

28,800

28,800

System Power KW

2.78

2.65

4.14

4.02

HSPF (Btu/Watts-hr)

6.75

6.95

6.80

6.90

Compressor

No./Type

1/Recip.

1/Recip.

1/Scroll

1/Scroll

Outdoor Sound Rating (dB)

3

82

82

85

85

Outdoor Coil — Type

Lanced

Lanced

Lanced

Lanced

Tube Size (in.) OD

.3125

.3125

.3125

.3125

Face Area (sq ft)

9.59

9.59

9.59

9.59

Rows/FPI

2/17

2/17

3/17

3/17

Refrigerant Control

Expansion Valve

Expansion Valve

Expansion Valve

Expansion Valve

Indoor Coil — Type

Lanced

Lanced

Lanced

Lanced

Tube Size (in.)

.3125

.3125

.3125

.3125

Face Area (sq ft)

6.17

6.17

6.68

6.68

Rows/FPI

3/16

3/16

3/16

3/16

Refrigerant Control

Short Orifice

Short Orifice

Short Orifice

Short Orifice

Drain Connection No./Size (in.)

1/¾ NPT

1/¾ NPT

1/¾ NPT

1/¾ NPT

Outdoor Fan — Type

Propeller

Propeller

Propeller

Propeller

No. Used/Diameter (in.)

1/22

1/22

1/22

1/22

Drive Type/No. Speeds

Direct/1

Direct/1

Direct/1

Direct/1

CFM

2,950

2,950

3,200

3,200

No. Motors/HP

1/.25

1/.25

1/.40

1/.40

Motor RPM

1,075

1,075

1,075

1,075

Direct Drive Indoor Fan — Type

FC Centrifugal

FC Centrifugal

FC Centrifugal

FC Centrifugal

No. Used

1

1

1

1

Diameter x Width (in.)

10 x 10

10 x 10

11 x 11

11 x 11

Drive Type/No. Speeds

Direct/2

Direct/2

Direct/2

Direct/2

No. Motors

1

1

1

1

Motor HP (Standard/Oversized)

.33/.50

.33/.50

.60/.80

.60/.80

Motor RPM (Low/High Speed)

950/1,060

950/1,060

930/1,000

930/1,000

Oversized Motor RPM (Low/High Speed)

1,100/1,145

1,100/1,145

1,000/1,100

1,000/1,100

Motor Frame Size (Standard/Oversized)

48/48

48/48

48/48

48/48

Belt Drive Indoor Fan — Type

FC Centrifugal

FC Centrifugal

No. Used

1

1

Diameter x Width (in.)

11 x 11

11 x 11

Drive Type/No. Speeds

Belt/Variable Speed

Belt/Variable Speed

No. Motors

1

1

Motor HP (Standard/Oversized)

1.00/ —

1.00/ —

Motor RPM (Standard/Oversized)

1,750/ —

1,750/ —

Motor Frame Size (Standard/Oversized)

56/ —

56/ —

Filters — Type Furnished

5

Throwaway

Throwaway

Throwaway

Throwaway

(No.) Size Recommended (in.)

(2) 20 x 25 x 1

(2) 20 x 25 x 1

(2) 20 x 25 x 1

(2) 20 x 25 x 1

Refrigerant Charge (Lbs of R-22)

4

6.5

6.8

9.4

10.2

Notes:
1. Cooling Performance and Heating Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb . Gross capacity does not include the effect of fan motor heat. ARI capacity is

net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Air-Source Unitary Heat Pump Equipment certification
program, which is based on ARI Standard 210/240.

2. SEER is rated at ARI conditions and in accordance with DOE test procedures.
3. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For more information refer to Table PD-25.
4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
5. Optional 2 inch pleated filters are also available.

Advertising