Heat performance, Performance data (3 ton) – Trane PKGP-PRC003-EN User Manual

Page 29

Advertising
background image

PKGP-PRC003-EN

29

Table PD-26 — 3 Ton Single Phase Heating Capacities (Net)

WSC036A1

At 1200 CFM

Outdoor

Instantaneous Heating Capacity (Btuh/1000)

Integrated Heating Capacity (Btuh/1000)

Total Power in Kilowatts at

Temp

at Indicated Indoor Dry Bulb Temp.

at Indicated Indoor Dry Bulb Temp.

1

Indicated Indoor Dry Bulb Temp.

F.

60

70

75

80

60

70

75

80

60

70

75

80

-8

9.9

8.8

8.1

7.5

8.9

7.9

7.3

6.8

2.32

2.36

2.38

2.39

-3

12.0

10.8

10.2

9.5

10.8

9.7

9.2

8.6

2.42

2.47

2.49

2.51

2

14.2

12.9

12.3

11.6

12.8

11.6

11.1

10.4

2.51

2.57

2.60

2.62

7

16.5

15.2

14.5

13.8

14.9

13.7

13.1

12.4

2.60

2.67

2.71

2.73

12

18.8

17.5

16.8

16.1

16.9

15.8

15.1

14.5

2.69

2.77

2.81

2.84

17

21.1

19.9

19.2

18.5

19.0

17.9

17.3

16.7

2.77

2.87

2.91

2.95

22

23.5

22.2

21.5

20.9

21.2

20.0

19.4

18.8

2.85

2.96

3.01

3.06

27

26.1

24.6

23.9

23.1

23.5

22.1

21.5

20.8

2.94

3.05

3.11

3.16

32

28.7

27.2

26.4

25.6

25.8

24.5

23.8

23.0

3.02

3.15

3.21

3.27

37

31.3

29.7

28.9

28.1

28.2

26.7

26.0

25.3

3.11

3.25

3.32

3.38

42

33.9

32.2

31.4

30.6

30.5

29.0

28.3

27.5

3.20

3.35

3.42

3.50

47

36.6

34.8

33.9

33.1

36.6

34.8

33.9

33.1

3.29

3.45

3.53

3.61

52

39.2

37.4

36.5

35.6

39.2

37.4

36.5

35.6

3.39

3.57

3.65

3.74

57

41.9

38.7

37.8

36.8

41.9

38.7

37.8

36.8

3.49

3.66

3.75

3.85

62

43.2

41.3

40.4

39.4

43.2

41.3

40.4

39.4

3.57

3.78

3.89

3.99

67

45.9

43.9

42.9

41.9

45.9

43.9

42.9

41.9

3.69

3.92

4.02

4.13

72

48.6

46.5

45.5

44.4

48.6

46.5

45.5

44.4

3.81

4.05

4.17

4.28

For other airflow conditions, see heating capacity correction factor (Table PD-39).
Net heating capacity and power input includes indoor fan heat at ARI esp. To obtain net heating at other conditions, subtract fan heat at this condition and add fan heat at new condition.
Note:
1. Integrated heating capacities and powers include the effects of defrost in the frost region. All heating capacities and power (kw) are at 70% OD relative humidity and demand defrost cycle.

Table PD-27 — 3 Ton Three Phase Heating Capacities (Net)

WSC036A3, A4, AW At 1200 CFM

Outdoor

Instantaneous Heating Capacity (Btuh/1000)

Integrated Heating Capacity (Btuh/1000)

Total Power in Kilowatts at

Temp.

at Indicated Indoor Dry Bulb Temp.

at Indicated Indoor Dry Bulb Temp.

1

Indicated Indoor Dry Bulb Temp.

F.

60

70

75

80

60

70

75

80

60

70

75

80

-8

9.6

8.6

8.1

7.5

8.6

7.7

7.3

6.8

2.14

2.21

2.23

2.25

-3

11.7

10.7

10.1

9.5

10.5

9.6

9.1

8.6

2.25

2.32

2.35

2.38

2

13.9

12.8

12.3

11.6

12.5

11.5

11.1

10.4

2.36

2.44

2.47

2.50

7

16.3

15.1

14.5

13.9

14.7

13.6

13.1

12.5

2.46

2.54

2.58

2.62

12

18.6

17.4

16.8

16.1

16.7

15.7

15.1

14.5

2.55

2.65

2.69

2.73

17

20.9

19.8

19.2

18.5

18.8

17.8

17.3

16.7

2.64

2.75

2.80

2.85

22

23.4

22.1

21.5

20.8

21.1

19.9

19.4

18.7

2.73

2.85

2.90

2.95

27

26.0

24.6

23.9

23.2

23.4

22.1

21.5

20.9

2.82

2.95

3.00

3.06

32

28.6

27.2

26.4

25.7

25.7

24.5

23.8

23.1

2.91

3.04

3.11

3.17

37

31.2

29.7

28.9

28.2

28.1

26.7

26.0

25.4

3.00

3.14

3.21

3.28

42

33.9

32.2

31.4

30.6

30.5

29.0

28.3

27.5

3.09

3.24

3.32

3.39

47

36.5

34.8

34.0

33.1

36.5

34.8

34.0

33.1

3.18

3.34

3.42

3.50

52

39.2

37.4

36.5

35.6

39.2

37.4

36.5

35.6

3.28

3.45

3.53

3.62

57

41.8

38.7

37.8

36.8

41.8

38.7

37.8

36.8

3.37

3.53

3.63

3.72

62

43.2

41.3

40.3

39.3

43.2

41.3

40.3

39.3

3.44

3.65

3.75

3.85

67

45.8

43.9

42.9

41.8

45.8

43.9

42.9

41.8

3.55

3.76

3.87

3.98

72

48.5

46.4

45.4

44.3

48.5

46.4

45.4

44.3

3.65

3.88

4.00

4.11

For other airflow conditions, see heating capacity correction factor (Table PD-39).
Net heating capacity and power input includes indoor fan heat at ARI esp. To obtain net heating at other conditions, subtract fan heat at this condition and add fan heat at new condition.
Note:
1. Integrated heating capacities and powers include the effects of defrost in the frost region. All heating capacities and power (kw) are at 70% OD relative humidity and demand defrost cycle.

Performance
Data

(3 Ton)

Advertising