Performance data (5 ton) – Trane PKGP-PRC003-EN User Manual

Page 23

Advertising
background image

PKGP-PRC003-EN

23

Performance
Data

(5 Ton)

Table PD-12 — Belt Drive Evaporator Fan Performance — 5 Ton — WSC060A3,A4,AW — Downflow Airflow

External Static Pressure (Inches of Water)

.10

.20

.30

.40

.50

.60

.70

.80

.90

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

1-HP Standard Motor & Field Supplied Low Static Drive (1)

1-HP Standard Motor & Drive

1600

703

0.36

757

0.41

806

0.47

854

0.52

899

0.58

944

0.65

985

0.73

1023

0.79

1060

0.86

1800

706

0.42

760

0.47

815

0.54

861

0.60

904

0.66

947

0.72

988

0.78

1028

0.86

1067

0.94

1104

1.02

2000

773

0.57

821

0.62

873

0.69

918

0.76

958

0.83

998

0.90

1036

0.96

1073

1.02

1111

1.10

1147

1.19

2200

840

0.75

885

0.80

930

0.87

977

0.95

1016

1.03

1053

1.10

1089

1.17

1124

1.24

1158

1.31

1191

1.39

2400

909

0.96

950

1.02

990

1.08

1034

1.16

1074

1.25

1110

1.00

1143

1.42

1177

1.50

Table PD-12 — Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

1-HP Standard Motor & Drive

1600

1093

0.92

1126

0.99

1160

1.06

1190

1.13

1222

1.20

1800

1138

1.10

1171

1.17

1203

1.25

1232

1.32

1262

1.39

2000

1182

1.28

1215

1.37

1246

1.46

2200

1226

1.48

2400

Table PD-13 — Belt Drive Evaporator Fan Performance — 5 Ton — WSC060A3,A4,AW — Horizontal Airflow

External Static Pressure (Inches of Water)

.10

.20

.30

.40

.50

.60

.70

.80

.90

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

1-HP Standard Motor & Field Supplied

1-HP Standard Motor & Drive

Low Static Drive (1)

1600

707

0.35

774

0.42

837

0.50

898

0.57

953

0.65

1001

0.72

1045

0.80

1087

0.87

1129

0.95

1168

1.03

1800

778

0.48

840

0.56

897

0.64

953

0.72

1008

0.81

1058

0.89

1102

0.98

1143

1.06

1181

1.15

1219

1.23

2000

850

0.65

908

0.73

961

0.81

1012

0.90

1062

1.00

1111

1.09

1157

1.19

1198

1.28

1237

1.37

1274

1.47

2200

923

0.84

978

0.93

1028

1.02

1075

1.12

1120

1.22

1166

1.32

1211

1.43

2400

997

1.07

1049

1.17

1096

1.27

1140

1.37

1183

1.48

Table PD-13 — Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

1-HP Standard Motor

1600

1206

1.12

1241

1.20

1275

1.28

1306

1.37

1338

1.46

1800

1256

1.32

1291

1.41

1326

1.50

2000

2200

2400

For Standard Evaporator Fan Speed (RPM), reference Table PD-20.
Notes:
Data includes pressure drop due to standardfilters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-23 to determine additional static pressure drop due to other
options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt may be
necessary.
Factory supplied motors, in commercial equipment, are definite purpose motors,
specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.

For Standard Evaporator Fan Speed (RPM), reference Table PD-20.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-23 to determine additional static pressure drop due to other
options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt may be
necessary.
Factory supplied motors, in commercial equipment, are definite purpose motors,
specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.

Advertising