(10 Ton)

Table PD-18 — Belt Drive Evaporator Fan Performance — 10-Ton — WSC120A3,A4,AW — Downflow Airflow

External Static Pressure (Inches of Water)

.10

.20

.30

.40

.50

.60

.70

.80

.90

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

2-HP Standard Motor & Field Supplied Low Static Drive (1)
3200

560

0.53

601

0.63

644

0.74

682

0.85

718

0.97

754

1.10

789

1.25

822

1.38

856

1.53

887

1.67

3600

620

0.73

657

0.83

694

0.95

731

1.08

764

1.20

797

1.33

829

1.48

860

1.63

892

1.79

922

1.95

4000

680

0.97

715

1.09

747

1.21

782

1.35

814

1.49

844

1.63

874

1.77

903

1.93

932

2.09

960

2.27

4400

741

1.27

773

1.40

803

1.53

834

1.67

864

1.82

894

1.98

922

2.13

948

2.28

975

2.44

1001

2.62

4800

803

1.62

833

1.76

861

1.90

887

2.04

916

2.20

972

2.55

997

2.71

1022

2.87

1046

3.04

2-HP Standard Motor & Drive

5-HP Oversized Motor & Drive

Table PD-18 — Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

2-HP Standard Motor & Drive

3200

917

1.82

945

1.97

973

2.14

999

2.30

1024

2.47

1048

2.65

1072

2.82

1095

3.00

1117

3.17

1140

3.36

3600

951

2.11

979

2.27

1007

2.43

1033

2.60

1059

2.78

1082

2.95

1107

3.14

1130

3.33

1152

3.52

1173

3.71

4000

988

2.44

1015

2.62

1042

2.79

1068

2.97

1093

3.15

1117

3.33

1142

3.52

1164

3.70

1187

3.91

1209

4.11

4400

1028

2.81

1053

3.00

1078

3.19

1103

3.38

1128

3.57

1152

3.77

1176

3.96

1198

4.15

1221

4.36

1243

4.56

4800

1071

3.23

1095

3.42

1119

3.62

1142

3.83

1166

4.04

1189

4.25

1212

4.46

1233

4.66

1256

4.88

1277

5.09

5-HP Oversized Motor & Drive

Table PD-19— Belt Drive Evaporator Fan Performance — 10-Ton — WSC120A3,A4,AW — Horizontal Airflow

External Static Pressure (Inches of Water)

.10

.20

.30

.40

.50

.60

.70

.80

.90

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

2-HP Standard Motor & Drive

3200

656

0.81

691

0.89

730

1.00

771

1.13

807

1.26

844

1.39

886

1.55

926

1.72

965

1.89

1000

2.06

3600

729

1.13

761

1.22

792

1.32

829

1.45

865

1.60

898

1.74

930

1.89

965

2.06

1002

2.24

1038

2.43

4000

802

1.52

833

1.63

860

1.73

890

1.86

923

2.01

956

2.17

986

2.30

1015

2.48

1044

2.65

1077

2.85

4400

876

1.99

905

2.12

931

2.24

955

2.35

983

2.49

1014

2.66

1045

2.84

1072

3.01

1098

3.18

1125

3.36

4800

950

2.56

977

2.70

1002

2.84

1025

2.96

1048

3.08

1074

3.24

1102

3.43

1131

3.63

1156

3.81

1181

4.00

5-HP Oversized Motor & Drive

Table PD-19 — Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

5-HP Oversized Motor & Drive

3200

1029

2.20

1057

2.35

1084

2.49

1108

2.63

1132

2.77

1155

2.91

1177

3.05

1198

3.18

1219

3.32

1239

3.46

3600

1072

2.62

1106

2.81

1134

2.98

1160

3.15

1185

3.31

1209

3.47

1231

3.63

1252

3.78

1274

3.94

1295

4.10

4000

1111

3.05

1143

3.26

1174

3.47

1204

3.68

1232

3.88

1260

4.09

1283

4.27

1306

4.46

1327

4.63

1349

4.81

4400

1152

3.55

1182

3.76

1211

3.99

1241

4.21

1270

4.44

1299

4.68

1327

4.91

1352

5.14

1377

5.37

1400

5.57

4800

1205

4.19

1229

4.39

1253

4.58

1280

4.81

1309

5.06

1336

5.31

1363

5.56

5-HP Oversized Motor& Field Supplied Sheave (2)

For Standard Evaporator Fan Speed (RPM), reference Table PD-20.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-23 to determine additional static pressure drop due to other options/accessories.
2-HP Fan Motor Heat (MBH) = 2.00 x Fan BHP + .500.
5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. Field Supplied Motor Sheave 1VP34 x 7/8”, Fan Sheave AK69,and belt AX35 required.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

2-HP Standard Motor & Field Supplied Low Static Drive (1)

For Standard Evaporator Fan Speed (RPM), reference Table PD-20.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-23 to determine additional static pressure drop due to other options/accessories.
2-HP Fan Motor Heat (MBH) = 3.00 x Fan BHP + .500.
5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. Field Supplied Motor Sheave 1VP34 x 7/8”, Fan Sheave AK69, and belt AX35 required.
2. Field supplied Fan Sheave BK95 required.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

Advertising