Electrical data, Electric power – Trane PKGP-PRC003-EN User Manual

Page 38

Advertising
background image

38

PKGP-PRC003-EN

Electrical
Data

Table ED-1 — Unit Wiring

Standard Indoor Fan Motor

Oversize Indoor Fan Motor

Optional Belt Drive Indoor Fan Motor

3

Unit

Minimum

Maximum Fuse

Minimum

Maximum Fuse

Minimum

Maximum Fuse

Unit

Operating

Circuit

Size or Maximum

Circuit

Size or Maximum

Circuit

Size or Maximum

Tons

Model No.

Voltage Range

2

Ampacity

Circuit Breaker

1

Ampacity

Circuit Breaker

1

Ampacity

Circuit Breaker

1

WSC036A1

187-253

26.2

40

28.6

45

N/A

N/A

3

WSC036A3

187-253

19.1

30

21.5

30

21.8

30

WSC036A4

414-506

9.9

15

11.1

15

11.3

15

WSC036AW

517-633

8.3

15

8.9

15

8.9

15

WSC048A1

187-253

39.7

60

41.8

60

N/A

N/A

WSC048A3

187-253

24.4

35

26.5

40

25.8

40

4

WSC048A4

414-506

12.1

15

13.7

20

12.9

20

WSC048AW

517-633

10.1

15

10.9

15

10.3

15

WSC060A1

187-253

48.7

60

50.4

60

N/A

N/A

WSC060A3

187-253

32.6

50

34.3

50

31.4

50

5

WSC060A4

414-506

16.6

25

16.9

25

16.2

25

WSC060AW

517-633

13.1

20

13.7

20

12.7

20

WSC072A3

187-253

32.2

50

33.5

50

6

WSC072A4

414-506

16.6

25

17.2

25

WSC072AW

517-633

12.5

15

13.5

20

WSC090A3

187-253

41.4

60

45.8

60

WSC090A4

414-506

21.9

35

24.0

35

WSC090AW

517-633

16.8

25

18.8

25

WSC120A3

187-253

50.4

60

57.5

70

10

WSC120A4

414-506

26.4

35

29.9

35

WSC120AW

517-633

21.0

25

23.9

30

Notes:
1. HACR breaker per NEC.
2. Heater KW ratings are at 208-240volt for 208-230 volt units.
3. Optional Belt Drive motor applies to 3-5 ton models only.

The standard motor for 6-10 ton models is belt drive.