The installation location chosen must:

Comply with all clearances listed below.

Provide suitable location for the exhaust and intake venting.

Not be installed in an unheated space.

Comply with all local codes and standards.

Note: Dimensions shown are minimums. Greater clearances will simplify

installation and service.

Figure 6.1

WARNING: Do not install the boiler on carpeting


If the boiler is to be installed in an enclosed room with no fresh air intake, the room must
have proper vent louvers installed. There should be two louvers, place each within 12” of
the ceiling and floor respectively. Each vent will have a free area of 54 square inches.

Outside

Air Opening

Air Opening

Each opening free area =
1 sq. inch per 2,000 BTU/h

0 to 12"

0 to 12"

Figure 6.2

When choosing an installation location insure the exhaust and intake pipes comply with
NFPA 54. The drawing on the next page illustrates the restrictions on exhaust locations.

6. Installation Location

1 2 . 8 in

10.0

i n

3 . 0 i n

2.0 i n

2.0 i n

C

LOSET IN

STA

LLA

TION

MINIMU M PER

MA

NAN T

C

LEA

RA

NCE

FR ON

TV IEW

SIDE V IEW CLOSET

INSTALLA TION

C

LOSET INSTA

LLA TION

SER

V IC

ECLEA

RA

N

CE

1 8 . 0 in

2 7 . 7 in

1 5 . 8 in

8 . 0 in

Note

: For boilers in an enclosed

space it is recommended to install
a CO detector in the boiler room.

RIVA HEAT ONLY MANUAL - REV A