Electrical connections/wiring cont – Verona WALL HUNG GAS BOILER User Manual

Page 24

Advertising
background image


12.3 Room Thermostat Connection:

• The room thermostat

must be connected to
the terminal block
situated next to the
control panel

1

2

L

N

3

To fused spur

isolation switch

Power supply
terminal block

External controls

terminal block

J

120 VAC Control
Terminal Block

Figure 12.6

Any external controls

and connection lines
must be rated at 120
VAC but under no
circumstances should
external live voltage
be connected to the
room thermostat link
on the boiler

• When connecting any

type of external
control, the jumper J
in Fig. 12.6 must be
removed.

• The room thermostat

must be connected to
the “Control Terminal
Block” (Fig 12.7).

Power supply
terminal block

External controls
terminal block

T

Room thermostat

1

2

L

N

3

(120V rating)

Figure 12.7

• Connect the room

thermostat between
terminals 1 and 3 as
shown in Fig. 12.7.

12.4 Relay Panel Connection:

• The relay control must

be connected to the
terminal block
situated next to the
control panel

1

2

L

N

3

To fused spur

isolation switch

Power supply
terminal block

External controls

terminal block

J

120 VAC Control
Terminal Block

Figure 12.8

• When connecting any

type of relay control,
the jumper J in Fig.
12.8 must be
removed.

• Connect the dry

contact switch of the
relay panel to the 120
VAC control terminal
block (Fig 12.9).

Power supply
terminal block

External controls
terminal block

Generic Relay Control

1

2

L

N

3

(120V rating)

T

Figure 12.9

• Connect the dry

contact switch to
terminals 1 and 3
shown in Fig. 12.9.








24

RIVA HEAT ONLY MANUAL - REV A

12. Electrical Connections/Wiring Cont.