Exhaust pipe location, Caution – Verona WALL HUNG GAS BOILER User Manual

Page 15

Advertising
background image



7. Exhaust Pipe Location

CAUTION

EXTERNAL VENT SURFACES ARE HOT.











The Exhaust Hood must be installed on the leeward side of house and conform to
the following guidelines:
1. The Vent hood shall not be less than 3 feet above any forced air inlet to the house.
2. The Vent hood shall not be less than 4 feet below, 4 feet horizontally, or 1 foot above

any door, window or gravity inlet into any building.

3. The Vent hood shall not be less than 2 feet from an adjacent building.
4. The Vent hood shall be not less than 7 feet above grade when located adjacent to

public walkway.

5. The Vent hood shall be located so that flue gasses are not directed to jeopardize

people, overheat combustible structures, materials or enter buildings.

6. Minimum of 4 feet horizontal clearance from electric meters, gas meters, regulators

and relief equipment.

7. All joints in system are to be sealed to prevent leakage of products of

combustion in the building.

8. Avoid installing exhaust hood on the North, West, or the side of the house receiving

the prevailing winds.

IT IS RESPONSABILITY OF THE HOMEOWNER TO KEEP THE VENT

TERMINAL CLEAR OF SNOW AND ICE

NOTE:

USE ONLY LISTED COMPONENTS SUPPLIED WITH THE BOILER.

SURFACE DISCOLORATION OF THE BUILDING MAY OCCUR DUE TO
IMPROPER INSTALLATION. QHT WILL NOT ACCEPT RESPONSIBILITY OR
LIABILITY FOR SUCH DISCOLORATION.